                Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the
                                    module correctly:
                                     Information  Description
                                     SN and version Identifier and SW version of the module
                                                  Address of the module, assigned to the module by a DHCP server at the time of
                                                  connection to the network in the case of configuration with a dynamic IP, or can
                                     IP address   be set via the menu in the event of a static IP
                                                       NOTE: without a DHCP server, the module automatically adopts a random IP
                                                     address within the 169.254.xxx.xxx range
                                                  Subnet mask; identifies the method for recognizing the subnet to which the
                                     Network Mask  modules belong and enables modules to be searched for within a defined set of
                                                  recipients.
                                     Gateway      IP address of the node to which the module is connected, in the presence of
                                     address      several subnets
                                                  Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
                                     MAC address
                                                  ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device



              Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
                                    communication:
                                     Information    Description                                         Default
                                                    Parameter for changing the configuration of the module from
                                                    Server Only to Client and Server and for integrating it into an
                                                    interactive data exchange network (see Ekip Com Hub on page
                                     Client/Server                                                      Server only
                                                    188).
                                                        IMPORTANT: if Client/Server, the module allows data
                                                        exchange like a normal Server function
                                                    Allows the IEEE 1588 protocol for distribution of the clock and
                                     Enable IEEE 1558                                                   Off
                                                    synchronization signal to be enabled .
                                                                                  (1)
                                                    Enables the module to be set up as a master in the the network
                                     IEEE 1558 Master                                                   Off
                                                    segment to which it belongs (synchronization clock).
                                     IEEE 1558 Delay   Allows the data exchange mode between module and master,   End-to- End
                                     mechanism      either Peer-to-Peer or End-to-End, to be selected.
                                                    Allows the SNTP protocol for distribution of the clock and
                                     Enable client SNTP                                                 Off
                                                    synchronization signal to be enabled  (1)
                                     ANTP Server    Allows the network server that supplies the SNTP to be set.  0.0.0.0
                                     address
                                     Time zone      Defines the time zone to be used for synchronism    +00:00
                                     Daylight Saving   Used to select whether daylight saving time is present (ON) or
                                     Time           not (OFF) in the country to which the synchronization time refers  Off
                                                    Permits (Enabled ARP) the periodic generation of a Gratuitous
                                     Disable Gratuitous   ARP message, used by Ekip Connect to rapidly find the modules   ARP
                                     ARP                                                                Enabled
                                                    via Ethernet scan without knowing the IP address beforehand
                                     Password       Enables the writing operations performed via the network to be   Standard
                                     protected access  protected by a password (Request password)       mode
                                     Password Modbus  With access protected by enabled password, this is the password  Local
                                     TCP            to use before each writing session .                access
                                                                                (2)
                                    (1)  Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
                                    (2)  the parameter can only be changed via system bus in the remote configuration