Page 32 - MCCB-XT2-XT4
P. 32

ABB | SACE Tmax XT

                         Test Menu                                      Description, parameters and Com-
                                     Menu             Submenus                                            Page
                                                                        mands
                                     Autotest         -                 Autotest command                  118
                                     Trip Test        -                 TRIP command                      118
                                     Test CB          -                 Close CB, Open CB                 118
                                     Ekip CI  (5)     -                 Autotest command                  119
                                                      Ekip Signalling 2K-1  (1)
                                     Ekip Signalling 2K  (1)  Ekip Signalling 2K-2  (1)  Module autotest command  119
                                                      Ekip Signalling 2K-3  (1)
                                                      S Protection  (3)
                                     ZoneSelectivity  (2)               Input, Force Output, Release Output  119
                                                      G Protection  (4)

                                    (1)  available if one or more Ekip Signalling modules are connected and detected by Ekip Touch
                                    (2)  available if Ekip Touch is on with auxiliary supply
                                    (3)  available with S and/or S2 and/or D protection enabled, for S protection the set curve must be t=k
                                    (4)  available with G and/or D protection enabled and curve t=k
                                    (5)  available if the Ekip CI module is connected and detected by Ekip Touch


                        About Menu   Menu               Submenus            Information provided
                                                                            Information about Ekip Touch: Trip unit serial
                                     Protection Unit    -                   number, type, version, standard, SW version,
                                                                            date and time, language
                                                                            CB information: TAG name, CB name, rated
                                     Circuit Breaker    -                   current, number of poles, CB status and
                                                                            position, total operations, CB serial number
                                                                            Status of 1% measurements (from Class 1 Power
                                     IEC 61557-12  (1)  -                   & Energy Metering package), serial number of
                                                                            assembly and current sensors connected
                                     Feature Collection  -                  List of tripped protections in Trip unit
                                                                            Module information: serial number, SW version,
                                     Modules            Modul x  (2)
                                                                            status of inputs/outputs/contacts (if present)
                                    (1)  available if Class 1 Power & Energy Metering SW package is provided for by Trip unit module or if it
                                    has been previously activated
                                    (2)  available if one or more modules are connected and detected by unit









































       30 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                          Ekip Touch - Interface and menus | 3 - Menu