1 - Protections - Introduction
Operating principle The protection functions are available with all Ekip Touch models and versions.
Each protection is associated with a different signal (current, voltages, frequencies, powers, etc) but the
operating principle is the same:
1. If the signal measured exceeds the set threshold, the specific protection activates (prealarm and/
or alarm).
2. The alarm appears on the display and, after a period of time (timing t ), depending on the
t
protection parameters set, can convert into a trip command (TRIP) transmitted to the internal
Trip coil of the CB.
NOTE:
• if the signal measured drops below the set threshold before the trip time has elapsed, Ekip
Touch quits the alarm and/or timing status and returns to the normal operating condition
• all protections have a default configuration: check the parameters and change to suit the
installation requirements before putting into service
TRIP When the Ekip CI module is present, Ekip M Touch allows a different TRIP configuration to be selected so
that, if a trip occurs, a contact of the Ekip CI module connected to an external remote control switch is
commanded (Normal mode).
NOTE: TRIP is always controlled by a command to the Trip Coil for protections I and G
Consult the parameters used with Ekip M Touch for further details (page 62).
References Many of the protection thresholds are displayed in two different quantities: absolute value and relative
value.
The relative value depends on the type of measurement:
Type of protection Reference Description
Current In Nominal size of the Trip unit
Voltage Un Line-to-line voltage setting
Frequency fn Frequency setting
Power Sn √3 x In x Un
Protections packages The protections described in the following chapters are grouped into packages, the availability of which
depends on the model and version of the Trip unit, and on their ability to be installed as additional
package:
Package Page
Standard Protections 35
Voltage protections 45
Voltage Advanced protections 48
Frequency protections 52
Power protections 55
ROCOF protections 61
Adaptive protections 62
Motor protections 63
Additional protections and functions 67