ABB | SACE Tmax XT

                       L Protection Function
                                    If the current of one or more phases exceeds threshold I1, the protection trips and, after a time established
                  t                 by the value read and by the parameter settings, transmits the TRIP command.
                       I1     L     To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  the summary table of the protections with the calculation formulas (page 75)
                            t1       •  the graph with trip curve (from page 78)
                                    Parameters
                                  I        NOTE: the limitations and default parameters of the Ekip M Touch Trip unit are different
                                           from those of the other models. Details are given after the table

                                     Parameter    Description                                         Default
                                                  Establishes curve dynamics and trip time calculation:
                                                   • t = k / I  according to IEC 60947-2.
                                                          2
                                                   • IEC 60255-151 SI
                                     Curve                                                            t = k/I  2
                                                   • IEC 60255-151 VI
                                                   • IEC 60255-151 EI
                                                   • t = k / I  according to 60255-151
                                                          4
                                                  Establishes the value that activates the protection and
                                                  contributes towards calculating the trip time.
                                     Threshold I1                                                     1 In
                                                  The value is given as both absolute value (A) and relative value (In)
                                                  and can be set within the range: 0.4 In to 1 In, in 0.001 In steps
                                                  Contributes towards calculating the trip time.
                                                  The value is given in seconds and can be set within the range: 3 s
                                     Time t1                                                          12 s
                                                  .. 60 s (for curve t = k / I ) or 3 s .. 9 s (for the other curves), in 1 s
                                                                     2
                                                  steps
                                                  Activates/deactivates the thermal memory function (page 67)
                                     Thermal          NOTE: the function is always ON with Ekip M Touch and   OFF
                                     memory
                                                     available with curve t = k / I  for all the other trip unit models
                                                                            2
                                                  Warns that the measured current is near to protection activation
                                                  threshold I1.
                                                  The value is given in percentage of threshold I1 and can be set
                                     Prealarm I1  within the range: 50% I1 to 90% I1, in 1% steps.    90 % I1
                                                      NOTA: the prealarm condition deactivates in two cases:
                                                       • current lower than prealarm threshold I1
                                                       • current higher than threshold I1

                                    Ekip M Touch
                                    With Ekip M Touch, L protection features the following differences compared to the other models:
                                     •  Curve: non-editable; specific for Ekip M Touch (page 81)
                                     •  Time t1: non-editable; determined by the Trip class (page 63)
                                     •  Thermal memory: always enabled, functions according to standard IEC 60255-8; thermal memory
                                       reset time is established by the Trip class (page 63)
                                     •  Different default parameters: t1 = 22 s (Class = 10E)
                                    Limitations and additional functions
                                     •  threshold I1 must be lower than threshold I2 (if S protection is activated)
                                     •  the trip time of the protection is forcibly set at 0.5 s if the calculation results give a lower theoretical
                                       value and/or if the current reading is more than 12 In
                                     •  with CB in UL standard configuration, the only available curve is t = k/I  2

























       36 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                               Protections | 2 - Standard Protections