       4 - Voltage Advanced protections



                               List The Advanced Voltage protections, configurable in all models as additional SW packages, are:
                                     Name           Type of protection              Page
                                                    Short-circuit with voltammetric
                                     S(V)                                           48
                                                    control
                                                    Short-circuit with voltammetric
                                     S2(V)                                          49
                                                    control
                                     RV             Residual voltage                51



                     S(V) Protection Function
                                    S(V) protection protects against short circuits, with a threshold sensitive to the value of the voltage.
                  t                 If the current of one or more phases exceeds threshold I20 for longer than time t20, the protection
                       I20    S(V)  activates and sends a TRIP command.
                                    Following a voltage drop, the I20 threshold varies according to two different modes:
                            t20      •  Step provides for a stepped variation, depending on parameters Ul and Ks.
                                     •  Lin (linear) provides for a dynamic variation, depending on parameters Ul, Uh and Ks.
                                  I      I20                                    I20


                                           I20                                    I20



                                      Ks x I20                                Ks x I20




                                                               Ul      V                    UI         Uh     V

                                    Figure 19
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  the summary table of the protections with the calculation formulas (page 76)
                                     •  the graph with trip curve (page 87)
                                    Parameters
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   OFF
                                                  managed as information
                                     Curve        Allows the operating mode, Step or Lin, to be selected  Scal
                                                  Establishes the value that activates the protection and
                                                  contributes towards calculating the trip time.
                                     Threshold I20  The value is given as both absolute value (amperes) and relative   1 In
                                                  value (In) and can be set within the range: 0.6 In to 10 In, in 0.1 In
                                                  steps



                                                                                                Continued on the next page














       48 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                        Protections | 4 - Voltage Advanced protections