Page 55 - MCCB-XT2-XT4
P. 55

ABB | SACE Tmax XT

                      OF Protection Function
                                    The protection sends a TRIP command if the grid frequency read by the unit exceeds threshold f13 for
                  t                 longer than t13.
                       f13   OF     The protection excludes itself if the maximum value of the line-to-line voltage is less than 30 V.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                            t13      •  summary table of the protections with the operating characteristics (page 76)
                                     •  the graph with trip curve (page 88)
                                 f  Parameters
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   OFF
                                                  managed as information
                                                  Establishes the value that activates the protection.
                                                  The value is given as both absolute value (Hertz) and relative
                                     Threshold f13                                                    1,1 Fn
                                                  value (Fn) and can be set within the range: 1 Fn to 1.1 Fn in 0.001
                                                  Fn steps
                                                  This is the trip time of the protection; the value is given in
                                     Time t13     seconds and can be set within a range: 0.06 s to 300 s, in 0.01 s   3 s
                                                  steps

                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 70).


                     UF2 Protection Function
                                    UF2 protection functions in the same way as UF protection: the protection sends a TRIP command if the
                  t                 grid frequency read by the unit drops below threshold f17 for longer than t17.
                              UF2
                        f17         It is independent of UF protection, thus thresholds and functions of the two protections can be
                                    programmed so as to take advantage of different plant solutions (example: signaling with UF and open
                    t17             command with UF2 or vice versa, or both for signaling or tripping).
                                    The protection excludes itself if the maximum value of the line-to-line voltage is less than 30 V.
                                 f  To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 75)
                                     •  the graph with trip curve (page 88)
                                    Parameters
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   OFF
                                                  managed as information
                                                  Establishes the value that activates the protection.
                                                  The value is given as both absolute value (Hertz) and relative
                                     Threshold f17                                                    0,9 Fn
                                                  value (Fn) and can be set within the range: 0.9 Fn to 1 Fn in 0.001
                                                  Fn steps
                                                  This is the trip time of the protection; the value is given in
                                     Time t17     seconds and can be set within a range: 0.06 s to 300 s, in 0.01 s   3 s
                                                  steps

                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 70).









       53 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                              Protections | 5 - Frequency protections