       5 - Frequency protections



                               List The Frequency protections, available by default for the Ekip Hi-Touch and Ekip M Touch models and
                                    configurable in the remaining models as additional SW package, are:
                                     Name                      Type of protection        Page
                                     UF                        Minimum frequency         52
                                     OF                        Maximum frequency         53
                                     UF2                       Minimum frequency         53
                                     OF2                       Maximum frequency         54



                      UF Protection Function
                                    The protection sends a TRIP command if the grid frequency read by the unit drops below threshold f12
                  t                 for longer than t12.
                              UF
                        f12         The protection excludes itself if the maximum value of the line-to-line voltage is less than 30 V.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                    t12              •  summary table of the protections with the operating characteristics (page 76)
                                     •  the graph with trip curve (page 88)
                                 f  Parameters
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   OFF
                                                  managed as information
                                                  Establishes the value that activates the protection.
                                                  The value is given as both absolute value (Hertz) and relative
                                     Threshold f12                                                    0,9 Fn
                                                  value (Fn) and can be set within the range: 0.9 Fn to 1 Fn in 0.001
                                                  Fn steps
                                                  This is the trip time of the protection; the value is given in
                                     Time t12     seconds and can be set within a range: 0.06 s to 300 s, in 0.01 s   3 s
                                                  steps

                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 70).