Page 53 - MCCB-XT2-XT4
P. 53

ABB | SACE Tmax XT

                      RV Protection Function
                                    The protection trips if loss of insulation occurs (verification of residual voltage U0); the protection sends
                  t                 a TRIP command if voltage U0 exceeds threshold U22 for longer than t2.
                       U22   RV     The protection is always available in the 4P configuration.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                            t22      •  summary table of the protections with the operating characteristics (page 76)
                                     •  the graph with trip curve (page 87)
                                 V  Parameters
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   OFF
                                                  managed as information
                                                  Establishes the value that activates the protection.
                                                  The value is given as both absolute value (V) and relative value
                                     Threshold U22                                                    0,15 Un
                                                  (Un) and can be set within the range: 0.05 Un to 0.5 Un in 0.001
                                                  Un steps
                                                  This is the trip time of the protection; the value is given in
                                     Time t22     seconds and can be set within a range: 0.05 s to 120 s, in 0.01 s   15 s
                                                  steps
                                                  This is the time the alarm is retained after the protection has
                                                  quit the alarm condition; it can be useful for keeping the timing
                                     Reset Time   activated when the protection is temporarily deactivated.  0 s
                                                  The value is given in seconds and can be set within the range: 0 s
                                                  to 0.2 s, in 0.02 s steps


                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 70).

















































       51 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                        Protections | 4 - Voltage Advanced protections
   48   49   50   51   52   53   54   55   56   57   58