Page 138 - MCCB-XT5
P. 138

Continued from the previous page                               ABB | SACE Tmax XT
                                     LEDs     Description
                                              Signals the on status and correct communication with Ekip Touch:
                                               • off: module off
                                               • on steady or flashing synchronized with the Power led of Ekip Touch: module on and
                                     Power
                                              communication with Trip unit present.
                                               • flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
                                              second): module on and communication with Trip unit absent
                                              Indicates the status of the communication between network master and module
                                              (slave):
                                     Rx
                                               • off: communication between master and module not activated
                                               • on steady: communication between master and module activated
                                              Indicates the status of the communication between network master and module
                                              (slave):
                                     Tx
                                               • off: communication between master and module not activated
                                               • on flashing: communication between master and module activated




                     Configurations Resistors can be connected to the RS-485 bus by configuring the dip-switches at the side of the module:


                                                                                                    ON




                                                                                                   1  2  3  4



                                    Figure 43

                                     Resistor   Dip        Description                                  Default
                                                           220 Ω termination resistor
                                     Rterm      1 and 2    Move dip-switches 1 and 2 to the ON position to   Off
                                                           connect Rterm
                                                           390 Ω pull-up or pull-down resistor
                                     Rpol       3 and 4    Move dip-switches 3 and 4 to the ON position to   Off
                                                           connect Rpol

                                           IMPORTANT: move the dip-switches before connecting the module to Ekip Supply and
                                           the communication network



            Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
                                    is available in the Settings menu (page 35).
                                    Two areas are activated if Ekip Touch detects the module correctly:
                                     •  information area in the About - Modules menu, containing the software version and serial number
                                       of the module
                                     •  specific configuration area in the Settings - Modules menu, where the following communication
                                       parameters can be configured:
                                     Parameter  Description                                             Default
                                                Module address; 1 to 126 range available
                                     Serial         IMPORTANT: devices connected to the same network must       (1)
                                     address                                                            125 / 124
                                                    have different addresses

                                    (1)  125 default of the Ekip Com Profibus DP module; 124 default of the Ekip Com Profibus DP
                                    Redundant module













       136 | © 2022 ABB |  1SDH002039A1002 - ECN000212994               External electronic accessories | 5 - Ekip Com Profibus DP
   133   134   135   136   137   138   139   140   141   142   143