Page 141 - MCCB-XT5
P. 141
ABB | SACE Tmax XT
Interface the module has three signaling leds:
1 2
Figure 44
LEDs Description
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on and
Power
communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with Trip unit absent
Indicates the communication status on the bus:
• off: device off line (with Status led off) , or in the error condition (with Status led
(1)
Network on)
Status (1) • on steady: device on line, and assigned to a master (operating condition)
• on flashing: device on line, but not assigned to a master (device ready to
communicate)
Indicates the communication status on the bus:
Network • Off: no error.
Status (2) • On fixed: device in bus off, or Network Power absent.
• On flashing: I/O connection (cyclic data) in timeout
(1) the device has not yet sent the Duplicate ID sequence in line
Configurations Resistors can be connected to the CAN bus by configuring the dip-switches at the side of the module:
ON
1 234
Figure 45
Resistor Dip Description Default
120 Ω termination resistor
Rterm 1 and 2 Move dip-switches 1 and 2 to the ON position to Off
connect Rterm
IMPORTANT:
• move the dip-switches before connecting the module to Ekip Supply and the network
• the termination resistors must never be included in the nodes; inclusion of this capacitance
could lead to a network with improper termination (impedance too high or too low), which
could potentially cause a failure. For example, removal of a node comprising a termination
resistor could lead to network failure
• the termination resistors must never be installed at the end of a drop line but only at the
ends of the main trunk line
139 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 External electronic accessories | 6 - Ekip Com DeviceNet TM