                      Power supply Ekip Com EtherNet/IP  is supplied directly by the Ekip Touch module to which it is connected.
                                                      TM
                                           NOTE: communication between Ekip Touch and the module is interrupted in the absence
                                           of auxiliary power supply


            Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
                                    is available in the Settings menu (page 35).
                                    The following communication parameters can be configured if the module has been correctly detected by
                                    Ekip Touch in the Settings-Modules menu:
                                     Parameter             Description                                  Default
                                                           Defines whether the module has the dynamic (Off) or
                                     Static IP address ON  static (On) IP address.                      Off
                                                           Se = On all the associated parameters are enabled
                                     Static address IP address  Enables the static IP to be selected    0.0.0.0
                                     Static Network Mask   Enables the subnet mask to be selected       0.0.0.0
                                                           When there are several subnets, enables the IP address
                                     Static Gateway address  of the node to which the module is connected to be   0.0.0.0
                                                           selected




                Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the
                                    module correctly:
                                     Parameter          Description
                                     SN and version     Identifier and SW version of the module
                                                        Address of the module, assigned to the module by a DHCP server at the
                                                        time of connection to the network in the case of configuration with a
                                     IP address         dynamic IP, or can be set via the menu in the event of a static IP
                                                             NOTE: without a DHCP server, the module automatically adopts a
                                                            random IP address within the 169.254.xxx.xxx range
                                                        Subnet mask; identifies the method for recognizing the subnet to which
                                     Network Mask       the modules belong and enables modules to be searched for within a
                                                        defined set of recipients.
                                                        IP address of the node to which the module is connected, in the presence
                                     Gateway address
                                                        of several subnets
                                                        Address assigned by ABB, with OUI (Organizationally Unique Identifier)
                                     MAC address        equal to ac:d3:64, which uniquely identifies the manufacturer of an
                                                        Ethernet device