Page 190 - MCCB-XT5
P. 190
ABB | SACE Tmax XT
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Allows the IEEE 1588 protocol for distribution of the
Enable IEEE 1558 Off
clock and synchronization signal to be enabled (NOTE)
Enables the module to be set up as a master in the the
IEEE 1558 Master network segment to which it belongs (synchronization Off
clock).
Allows the data exchange mode between module
IEEE 1558 Delay and master, either Peer-to-Peer or End-to-End, to be End-to-End
mechanism
selected.
Allows the SNTP protocol for distribution of the clock
Enable client SNTP Off
and synchronization signal to be enabled (NOTE) .
Allows the network server that supplies the SNTP to be
ANTP Server address 0.0.0.0
set.
Time zone Defines the time zone to be used for synchronism +00:00
Used to select whether daylight saving time is
Daylight Saving Time present (ON) or not (OFF) in the country to which the Off
synchronization time refers
Parameter useful if an IEEE 1588 GrandMaster clock is
not available:
• If enabled (ON), the module is seen as an IEEE1588
master clock by all the slaves/devices in the same local
IEEE 1588 Boundary clock OFF
network, even when the source of external synchronism
is different from IEEE 1588 (SNTP for example)
• If disabled (OFF) the module benefits from the
synchronism of the master in its own network)
Enables the Rate limiter function, which limits the
Enable package Limitation number of packages entering the module from the Disable
network, to be activated/deactivated
NOTE: Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description
HW and Boot version general module information
Flash CRC status and result Information about the correctness of the SW in the module
Ekip Link status Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server Synchronization State of synchronism with SNTP server
Valid with Master IEEE 1588= ON, notifies the presence (Slave
IEEE 1558 status or PTP Master Active) or absence (PTP Master but Passive) of a
higher level master
188 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 Internal accessories | 4 - Ekip Com EtherNet/IP TM