Page 204 - MCCB-XT5
P. 204

ABB | SACE Tmax XT

       9 - Ekip Maintenance



                                    Ekip Maintenance is a signaling accessory allowing a programmable input and a programmable output
                                    to be managed.
                                    The module can be configured in the CB according to standard UL; the menus and information about the
                                    module are available in the Trip unit with the names of the respective module for the IEC standard (Ekip
                                    Signalling 1K).
                                           IMPORTANT: each circuit-breaker can house one module only; configuration with external
                                           modules is not allowed if an internal module is present




                       Connections The circuit diagrams and references concerning the terminals are available in document 1SdM000005A1001.
                                    To connect the module to Ekip Touch and to actuator MOE-E if present, please consult document
                                    1SdH002011A1507.


                      Power supply Ekip Maintenance is supplied directly by the Ekip Touch to which it is connected.
                                           NOTE: communication between Ekip Touch and the module is interrupted in the absence
                                           of auxiliary power supply



                              Input The input can be configured so that its status corresponds to actions or signals, with different
                                    programming options (see Menu).
                                    The module permits two logic statuses, interpreted differently by the Trip unit on the basis of the selected
                                    configuration:
                                     Parameter    Description  Contact configuration     Status detected by Trip unit
                                                               Active open               ON
                                     Open         Circuit open  (1)
                                                               Active closed             OFF
                                                               Active open               OFF
                                     Close        Short-circuit  (2)
                                                               Active closed             ON
                                    (1)  R > 100 kΩ
                                    (2)  R (wiring + short circuit contact) <25 Ω


                            Output The output has three contacts: normally open (NO), normally closed (NC) and common
                                    The output can be configured so that the contacts change status when one or more events occur, with
                                    different programming options (see Menu).
                                    Compared to the common contact, the NO and NC contacts have the following electrical characteristics:
                                     Characteristics                        Maximum limit  (1)
                                     Maximum switchable voltage             150 VDC / 250 VAC.
                                                                            2 A @ 30 VDC, 0,8 A @ 50 VDC, 0,2 A @ 150 VDC,
                                     Breaking capacity
                                                                            4 A @ 250 VAC
                                     Dielectric strength between contact and internal   1000 V AC (1 minute @ 50 Hz).
                                     coil

                                    (1)  data relating to a resistive load