                   Input parameters The input can be configured in the Settings-Modules-Ekip Signalling 1K-Input menu:
                                     Parameter    Description                                         Default
                                                  Defines whether the input is interpreted as ON by the Trip unit
                                     Polarity                                                         Active closed
                                                  when it is open (Active open) or when it is closed (Active Closed)
                                                  Minimum activation time of the input before status change is
                                                  recognized; the delay is given in seconds and can be set within
                                                  range: 0 s to 100 s, in 0.01 s steps
                                     Delay             NOTES :                                        0.1 s
                                                      • status change is not recognized if the input deactivates
                                                     before this time has elapsed
                                                      • if delay = 0 s status change must still be more than 300 µS




                 Output parameters The output can be configured in the Settings-Modules-Ekip Signalling 1K-Output menu:
                                     Parameter    Description                                         Default
                                                  Event which activates the output and switches the contacts.
                                                  Different protection proposals, statuses and thresholds are
                                     Signal source  available on the display; the Custom mode can be configured via  None
                                                  Ekip Connect so as to extend the solutions and combine several
                                                  events
                                                  Minimum duration of the presence of the source before the
                                                  output is activated; the delay is given in seconds and can be set
                                                  within range: 0 s to 100 s, in 0.01 s steps
                                                       NOTE:
                                     Delay                                                            0 s
                                                      • the output will not be switched if the source is deactivated
                                                     before this time has elapsed
                                                      • if delay = 0 s the source must still be present for longer
                                                     than 300 µS
                                                  Defines the rest status of the contact with source not present
                                     Contact Type                                                     NO
                                                  between: open (NO) and closed (NC)
                                                  Allows the output (and relative status led) to be kept activated
                                     Latched                                                          Off
                                                  (On) or deactivated (Off) when the event disappears
                                                  Defines the minimum closing time of the contact following the
                                                  rapid presence of sources
                                                   • Source duration < min. activation = contact is activated for the
                                     min Activation
                                     Time         minimum activation time                             0 ms
                                                   • Source duration ≥ min. activation = contact is activated for as
                                                  long as the source persists
                                                  Choose between: 0 ms, 100 ms, 200 ms



                             About The About-Modules menu contains the specific menu of the module, in which the statuses of the input
                                    (On/Off) and output (Open/Closed) are present.


                               Test The output test command can be executed in the Test menu (see page 125).