Page 77 - MCCB-XT5
P. 77

Continued from the previous page                               ABB | SACE Tmax XT
                                    Configuration
                                    To correctly configure selectivity D in a ring system:
                                     1. Connect the zone selectivity outputs of each device (example: DFin) to the selectivity input of the same
                                    direction as the device immediately after (example: DFout).
                                     2. Connect all the Szc of devices in the same network together.
                                    Logic table
                                    The table includes all cases in which, with zone selectivity enabled in the device, an alarm condition occurs
                                    or a zone selectivity signal is received from another device.
                                    The Forward output is activated if the fault direction coincides with the reference direction otherwise, if
                                    it is in the opposite direction, the Backward output is activated (page 62)
                                     Fault di-                             Tripping
                                     rection  Condition DFin Dbin Dfout Dbout  time  Remarks
                                     Forward  If < I7 Fw  0  x   0    x    No TRIP  Device not in alarm status
                                     Backward  If < I7 Bw  x  0  x    0
                                     Forward  If < I7 Fw  1  x   1    x             The device is not in the alarm
                                                                                    status, but sends the selecitivity
                                                                           No TRIP
                                     Backward  If < I7 Bw  x  1  x    1             signal received to the output of the
                                                                                    reference direction
                                     Forward  If > I7 Fw  0  x   1    x    t7 Fw sel  The device is in the alarm status and
                                                                                    is the first to detect the fault: trips
                                     Backward  If > I7 Bw  x  0  x    1    t7 Bw sel
                                                                                    within time t7 Fw sel or t7 Bw sel
                                     Forward  If > I7 Fw  1  x   1    x    t7 Fw    The device is in the alarm status but
                                                                                    is not the first to detect the fault:
                                     Backward  If > I7 Bw  x  1  x    1    t7 Bw
                                                                                    trips within time t7 Fw (or t7 Bw)

                                           NOTE: when zone selectivity is active and the direction of the fault cannot be established,
                                           the unit trips by considering the first threshold to be exceeded between I7 Fw and I7 Bw,
                                           without activating any output (DFout or Dbout).; if both the thresholds have been exceeded
                                           (for example, if they have been set with the same value), the unit trips after the shortest
                                           time between t7 Fw and t7 Bw.



              Trip Only Forward and  D protection can be configured (if available and enabled) with 2 additional parameters via the service
                          Backward connector (via Ekip Connect) or via system bus communication:
                                     •  Trip only Forward: if activated, D protection only controls open commands if forward direction is
                                       detected
                                     •  Trip only Backward: if activated, D protection only controls open commands if backward direction
                                       is detected
                                    faults in the opposite direction are only handled as alarm information.


                  Type of selectivity The zone selectivity inputs and certain of the outputs can be configured via service connector (via Ekip
                                    Connect) or via system bus communication for protections S, S2, I, 2I, MCR, G and D (if available and
                                    enabled):
                                     •  Standard: operation as by zone selectivity standard logic (default configuration)
                                     •  Customized: the event that activates the zone selectivity input or output can be selected in this mode.
                                           IMPORTANT: in the Customized configuration, the only zone selectivity activation event
                                           is the one set and standard selectivity operation is therefore not active (changes should
                                           only be made by expert technical personnel).




















       75 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                  Protections | 10 - Additional protections and functions
   72   73   74   75   76   77   78   79   80   81   82