Page 100 - B_ELSB_Cat_2022_01_MCBs
P. 100
1/100 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: selectivity
MCCB XT3@415V - SN201 @230/240V
Supply S. XT3
Version N,S
Release TM
Load S. Char Icu [kA] In[A] 63 80 100 125 160 200 250
≤ 4 T T T T T T T
6 T T T T T T T
10 T T T T T T T
16 5 T T T T T T
SN201 L B,C 6
20 5 T T T T T T
25 5 T T T T T T
32 T T T T T T
40 T T T T T T
≤ 4 T T T T T T T
6 T T T T T T T
8 7,5 8,5 T T T T T
10 7,5 8,5 T T T T T
13 5 7,5 T T T T T
SN201 B,C,D,K 10
16 5 7,5 T T T T T
20 5 6 T T T T T
25 5 6 T T T T T
32 6 7,5 T T T T
40 6 7,5 T T T T
≤ 4 T T T T T T T
6 T T T T T T T
10 7,5 8,5 T T T T T
13 5 7,5 T T T T T
SN201 M B,C 10 16 5 7,5 T T T T T
20 5 6 T T T T T
25 5 6 T T T T T
32 6 7,5 T T T T
40 6 7,5 T T T T
Value valid in case of Supply S. breaker only magnetic
Tmax T1 – S800S @400/415 V
Supply s. T1
Char. B, C, N
Trigger TM
Icu [kA] Iu [A] 160
Load s.
In [A] 16 20 25 32 40 50 63 80 100 125 160
10 4.5 4.5 4.5 4.5 8 10 20* 25* 36*
13 4.5 4.5 4.5 7.5 10 15 25* 36*
16 4.5 4.5 7.5 10 15 25* 36*
20 4.5 7.5 10 15 25* 36*
25 6 10 15 20* 36*
32 7.5 10 20* 36*
S800S B , C, D, K 50
40 10 20* 36*
50 15 36*
63 36*
80 36*
100 36*
125