Page 98 - B_ELSB_Cat_2022_01_MCBs
P. 98
1/98 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: selectivity
MCCB XT1@415V - SN201 @230/240V
Supply
S. XT1
Version B,C,N,S,H
Release TM
Load S. Char Icu [kA] In[A] 16 20 25 32 40 50 63 80 100 125 160
≤ 4 T T T T T T T T T T T
6 T T T T T T T T T T T
10 3 3 3 4,5 T T T T T
16 3 4,5 5 T T T T
SN201 L B,C 6
20 3 5 T T T T
25 5 T T T T
32 T T T T
40 T T T
≤ 4 T T T T T T T T T T T
6 6 6 6 6 6 6 T T T T T
8 3 3 3 4,5 7,5 8,5 T T T
10 3 3 3 4,5 7,5 8,5 T T T
13 3 4,5 5 7,5 T T T
SN201 B,C,D,K 10
16 3 4,5 5 7,5 T T T
20 3 5 6 T T T
25 5 6 T T T
32 6 7,5 T T
40 7,5 T T
≤ 4 T T T T T T T T T T T
6 6 6 6 6 6 6 T T T T T
10 3 3 3 4,5 7,5 8,5 T T T
13 3 4,5 5 7,5 T T T
SN201
M B,C 10 16 3 4,5 5 7,5 T T T
20 3 5 6 T T T
25 5 6 T T T
32 6 7,5 T T
40 7,5 T T