Page 101 - B_ELSB_Cat_2022_01_MCBs
P. 101
1
1/101
—
MCBs technical details
Coordination tables: selectivity
MCCB XT4@415V - SN201 @230/240V
Supply
S. XT4
Version N,S,H,L,V
Release TM EL
Load S. Char Icu [kA] In[A] 20 25 32 40 50 63 80 100 125 160 200 225 250 40 63 100 160 250
≤ 4 T T T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T T T
10 3 3 3 3 4,5 T T T T T T T T 3 T T T T
16 3 3 4,5 5 T T T T T T T 3 T T T T
SN201 L B,C 6
20 3 3 5 T T T T T T T T T T T
25 3 5 T T T T T T T T T T T
32 3 T T T T T T T T T T T
40 T T T T T T T T T T
≤ 4 T T T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T T T
8 3 1 3 3 3 4,5 7,5 8,5 T T T T T T 3 T T T T
10 3 3 3 3 4,5 7,5 8,5 T T T T T T 3 T T T T
13 3 3 4,5 5 7,5 T T T T T T 3 T T T T
SN201 B,C,D,K 10
16 3 3 4,5 5 7,5 T T T T T T 3 T T T T
20 3 3 5 6 T T T T T T T T T T
25 3 5 6 T T T T T T T T T T
32 3 6 7,5 T T T T T T T T T
40 6 7,5 T T T T T T T T
≤ 4 T T T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T T T T
10 3 3 3 3 4,5 7,5 8,5 T T T T T T 3 T T T T
13 3 3 4,5 5 7,5 T T T T T T 3 T T T T
SN201
M B,C 10 16 3 3 4,5 5 7,5 T T T T T T 3 T T T T
20 3 3 5 6 T T T T T T T T T T
25 3 5 6 T T T T T T T T T T
32 3 6 7,5 T T T T T T T T T
40 6 7,5 T T T T T T T T
Value valid in case of Supply S. breaker only magnetic
Tmax T3 – S800S @400/415 V
Supply s. T3
Char. N, S
Trigger TM
Icu [kA] Iu [A] 250
Load s.
In [A] 63 80 100 125 160 200 250
10 8 10 20 25 36 36 50*
13 7.5 10 15 25 36 36 50*
16 7.5 10 15 25 36 36 50*
20 7.5 10 15 25 36 36 50*
25 6 10 15 20 36 36 50*
32 7.5 10 20 36 36 50*
S800S B , C, D, K 50
40 10 20 36 36 50*
50 15 36 36 50*
63 36 36 50*
80 36 50*
100 50*
125 50*