Page 99 - B_ELSB_Cat_2022_01_MCBs
P. 99
1
1/99
—
MCBs technical details
Coordination tables: selectivity
MCCB XT2@415V - SN201 @230/240V
Supply
S. XT2
Version N,S,H,L,V
Release TM EL
Load S. Char Icu [kA] In[A] 16 20 25 32 40 50 63 80 100 125 160 10 25 63 100 160
≤ 4 T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T
10 3 3 3 3 4,5 T T T T T T T T T
16 3 3 4,5 5 T T T T T T T
SN201 L B,C 6
20 3 3 5 T T T T T T T
25 3 5 T T T T T T T
32 3 T T T T T T T
40 T T T T T T
≤ 4 T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T
8 3 3 3 3 4,5 7,5 8,5 T T T T T T T
10 3 3 3 3 4,5 7,5 8,5 T T T T T T T
13 3 3 4,5 5 7,5 T T T T T T
SN201 B,C,D,K 10
16 3 3 4,5 5 7,5 T T T T T T
20 3 3 5 6 T T T T T T
25 3 5 6 T T T T T T
32 3 6 7,5 T T T T T
40 6 1 7,5 T T T T
≤ 4 T T T T T T T T T T T T T T T T
6 T T T T T T T T T T T T T T T
10 3 3 3 3 4,5 7,5 8,5 T T T T T T T
13 3 3 4,5 5 7,5 T T T T T T
SN201
M B,C 10 16 3 3 4,5 5 7,5 T T T T T T
20 3 3 5 6 T T T T T T
25 3 5 6 T T T T T T
32 3 6 7,5 T T T T T
40 6 1 7,5 T T T T
Value valid in case of Supply S. breaker only magnetic