Page 173 - B_ELSB_Cat_2022_01_MCBs
P. 173
1
1/173
—
MCBs technical details
Coordination tables: selectivity
TmaxXT - S300P @ 415V AC
Supply s. XT4
Char. Version N, S, H, L, V, X
Relay TM
Iu [A] 250
Load s. Icu [kA] 36, 50, 70, 120, 150
In [A] 20 25 32 40 50 63 80 100 125 160 200 225 250
0,5...4 T T T T T T T T T T T T T
6 7.5 7.5 7.5 7.5 7.5 10 T T T T T T T
8 7.5 7.5 7.5 7.5 7.5 10 T T T T T T T
10 3 5 5 5 6.5 7.5 9 T T T T T T
13 5 5 5 6.5 7.5 8 T T T T T T
16 3 5 5 5 6.5 8 T T T T T T
S300P B, C 25
20 5 5 5 7.5 T T T T T T
25 5 5 7.5 T T T T T T
32 5 7.5 15 15 15 15 15 15
40 6.5 15 15 15 15 15 15
50 15 15 15 15 15 15
63 5 7.5 15 15 15 15
TmaxXT - S300P @ 415V AC
Supply s. XT2
Char. Version N, S, H, L, V
Relay EL
Iu [A] 160
Load s. Icu [kA] 36, 50, 70, 120, 150
In [A] 20 25 32 40 50
0,5...4 T25 T25 T25 T25 T25
6 T25 T25 T25 T25
8 T25 T25 T25 T25
10 T25 T25 T25 T25
13 T25 T25 T25 T25
16 T25 T25 T25
S300P B, C 25
20 T25 T25 T25
25 T25 T25 T25
32 15 15 15
40 15 15
50 10 10
63 6
TmaxXT - S300P @ 415V AC
Supply s. XT4
Char. Version N, S, H, L, V
Relay EL
Iu [A] 250
Load s. Icu [kA] 36, 50, 70, 120, 150
In [A] 40 63 100 160 250 250
0,5...4 T25 T25 T25 T25 T25 10
6 T25 T25 T25 T25 T25 10
8 T25 T25 T25 T25 T25 10
10 T25 T25 T25 T25 T25 10
13 T25 T25 T25 T25 T25 10
16 T25 T25 T25 T25 T25 10
S300P B, C 25
20 T25 T25 T25 T25 T25 10
25 T25 T25 T25 T25 10
32 15 15 15 15 10
40 15 15 15 10
50 15 15 15 10
63 15 15 15 10