Page 53 - B_ELSB_Cat_2022_01_MCBs
P. 53

1
                                                                                                            1/53



          —
          MCBs technical details
          Coordination tables


                                                              Selective protection
          Back-up protection                                  The tables given provide the value (in kA, referring to the
          The tables given provide the value (in kA, referring to the   breaking capacity according to the IEC 60947-2 Standard)
          breaking capacity according to the IEC 60947-2 Standard)    for which the selective protection is verified among the
          for which the back-up protection among the combination    combination of selected circuit-breakers. The tables cover
          of selected circuit-breakers is verified. The tables cover    the possible combinations between ABB SACE Tmax series
          the possible combinations between ABB SACE Tmax series    of moulded-case circuit-breakers, and the ABB series
          of moulded-case circuit-breakers and those between     of modular circuit-breakers. The values in the table
          the above-mentioned circuit-breakers and the ABB series    represent the maximum value obtainable of discrimination
          of modular circuit-breakers.                        between supply side circuit-breaker and load side circuit-
          The values indicated in the tables refer to the voltage:  breaker referring to the voltage:
          •  Vn of 230/240 V AC for coordination with modular SN 201   •  Vn of 230/240 V AC for the SN 201 circuit-breakers and Vn
           circuit-breakers                                    of 400/415 V AC for the supply side circuit-breakers in
          •  Vn of 400/415 V AC for all the other coordinations.  the coordination between MCB with the modular SN 201
                                                               circuit-breakers (see picture).
                                                              •  Vn of 400/415 V AC for all the other coordinations.


                L1  L2  L3 N


               400 V
          400 V
               400 V
               230 V



                            L3 N
          Note
          The following tables give the breaking capacities at 415 V AC for circuit-breakers SACE Tmax.

          Tmax @ 415 V AC
          Version                                              Icu [kA]
          B                                                    16
          C                                                    25
          N                                                    36
          S                                                    50
          H                                                    70
          L (T2)                                               85
          L (T4, T5)                                           120
          V                                                    200

          Caption                                              For miniature circuit-breakers:
          MCB   = miniature circuit-breakers  (SN 201, S 2, S 800)  B   =   trip characteristic (Im=3...5In)
          MCCB  = moulded-case circuit-breakers (Tmax)         C   =   trip characteristic (Im=5...10In)
                                                               D   =   trip characteristic (Im=10...20In)
          For moulded-case or air circuit-breakers:            K   =   trip characteristic (Im=10...14In)
          TM  =   thermomagnetic release                       Z   =   trip characteristic (Im=2...3In)
             –   TMD (Tmax)
             –   TMA (Tmax)                                    For solutions not shown in these tables, please consult
          M  =   magnetic only release                         the website: http://bol.it.abb.com or contact ABB SACE
             –   MF (Tmax)
             –   MA (Tmax)                                     For solutions not shown in these tabels referring to
          EL  =   electronic release                           SMISSLINE or S800 please use: leaflet 2CCC451039L02xx
             –   PR221DS - PR222DS (Tmax)
   48   49   50   51   52   53   54   55   56   57   58