Page 55 - B_ELSB_Cat_2022_01_MCBs
P. 55
1
1/55
—
MCBs technical details
Coordination tables: back-up
MCB - MCB @ 415 V
Supply S. S200 S200M S200P
Char. B-C B-C B-C
Load S. Icu [kA] 10 15 25 15
In [A] 0.5..63 0.5..63 0.5..25 32..63
S200 B,C,K,Z 10 0.5..63 15 25 15
S200M B,C 15 0.5..63 25
B,C, 25 0.5..25
S200P
D,K,Z 15 32..63
S800S – SN201 @ 230/240 V
Supply s. S800S
Char. B, C, D, K
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
SN201 B, D 10 6 50 50 50 50 50 50 50 50
10 50 50 50 50 50 50 50 50
16 50 50 50 50 50 50 50 50
20 50 50 50 50 50 50 50
25 50 50 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50
S800S – SN201 @ 230/240 V
Supply s. S800S
Char. B, C, D, K
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
SN201 C 10 2 50 50 50 50 50 50 50 50
4 50 50 50 50 50 50 50 50
6 50 50 50 50 50 50 50 50
10 50 50 50 50 50 50 50 50
16 50 50 50 50 50 50 50 50
20 50 50 50 50 50 50 50
25 50 50 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50