          MCBs technical details
          Coordination tables: back-up




          MCB - MCB @ 415 V
                                Supply S. S200            S200M             S200P
                 Char.                  B-C               B-C               B-C
          Load S.        Icu [kA]       10                15                25                15
                                In [A]  0.5..63           0.5..63           0.5..25           32..63
          S200   B,C,K,Z  10    0.5..63                   15                25                15
          S200M  B,C     15     0.5..63                                     25
                 B,C,    25     0.5..25
          S200P
                 D,K,Z   15     32..63

          S800S – SN201 @ 230/240 V
                           Supply s.        S800S
                   Char.                    B, C, D, K
          Load s.          Icu [kA]         50
                                    In [A]  25       32      40       50      63       80      100      125
          SN201    B, D    10       6       50       50      50       50      50       50      50       50
                                    10      50       50      50       50      50       50      50       50
                                    16      50       50      50       50      50       50      50       50
                                    20               50      50       50      50       50      50       50
                                    25                       50       50      50       50      50       50
                                    32                                50      50       50      50       50
                                    40                                        50       50      50       50

          S800S – SN201 @ 230/240 V
                           Supply s.        S800S
                   Char.                    B, C, D, K
          Load s.          Icu [kA]         50
                                    In [A]  25       32      40       50      63       80      100      125
          SN201    C       10       2       50       50      50       50      50       50      50       50
                                    4       50       50      50       50      50       50      50       50
                                    6       50       50      50       50      50       50      50       50
                                    10      50       50      50       50      50       50      50       50
                                    16      50       50      50       50      50       50      50       50
                                    20               50      50       50      50       50      50       50
                                    25                       50       50      50       50      50       50
                                    32                                50      50       50      50       50
                                    40                                        50       50      50       50
   50   51   52   53   54   55   56   57   58   59   60