Coordination tables: back-up
S800S – SN201 L @ 230/240 V
Supply s. S800S
Char. B, C, D, K
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
SN201 L B, C 6 2 50 40 25 25 18 15 15 15
4 50 40 25 25 18 15 15 15
6 50 40 25 25 18 15 15 15
10 50 40 25 25 18 15 15 15
16 50 40 25 25 18 15 15 15
20 40 25 25 18 15 15 15
25 25 25 18 15 15 15
32 25 18 15 15 15
40 18 15 15 15
S800S – SN201 M @ 230/240 V
Upstream S800S
Char. B, C, D, K
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
SN201 M B 10 6 50 50 50 50 50 50 50 50
10 50 50 50 50 50 50 50 50
16 50 50 50 50 50 50 50 50
20 50 50 50 50 50 50 50
25 50 50 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50
S800S - SN201 M @ 230/240 V
Supply s. S800S
Char. B, C, D, K
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
SN201 M C 10 2 50 50 50 50 50 50 50 50
4 50 50 50 50 50 50 50 50
6 50 50 50 50 50 50 50 50
10 50 50 50 50 50 50 50 50
16 50 50 50 50 50 50 50 50
20 50 50 50 50 50 50 50
25 50 50 50 50 50 50
32 50 50 50 50 50