Page 58 - B_ELSB_Cat_2022_01_MCBs
P. 58
1/58 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: back-up
S800S – S200M @230/400 V
Supply s. S800S
Char. B, C, D, K
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
S200M B 15 6...16 50 50 50 50 50 50 50 50
20 50 50 50 50 50 50 50
25 50 50 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50
50 50 50 50
63 50 50
Supply s. S800S
Char. B, C, D, K
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
S200M C 15 0.5...16 50 50 50 50 50 50 50 50
20 50 50 50 50 50 50 50
25 50 50 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50
50 50 50 50
63 50 50
S800S – S200P @230/400 V
Supply s. S800S
Char. B, C, D, K
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
S200P B 25 6...16 50 50 50 50 50 50 50 50
20 50 50 50 50 50 50 50
25 50 50 50 50 50 50
15 32 50 50 50 50 50
40 50 50 50 50
50 50 50 50
63 50 50
Supply s. S800S
Char. B, C, D, K
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
S200P C 25 0.5...16 50 50 50 50 50 50 50 50
20 50 50 50 50 50 50 50
25 50 50 50 50 50 50
15 32 50 50 50 50 50
40 50 50 50 50
50 50 50 50
63 50 50