Page 62 - B_ELSB_Cat_2022_01_MCBs
P. 62
1/62 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: back-up
S800N – S200M @ 230/400 V
Supply s. S800N
Char. B, C, D
Load s. Icu [kA] 36
In [A] 25 32 40 50 63 80 100 125
S200M B 15 6…16 36 36 36 36 36 36 36 36
20 36 36 36 36 36 36 36
25 36 36 36 36 36 36
32 36 36 36 36 36
40 36 36 36 36
50 36 36 36
63 36 36
Supply s. S800N
Char. B, C, D
Load s. Icu [kA] 36
In [A] 25 32 40 50 63 80 100 125
S200M C 15 0.5…16 36 36 36 36 36 36 36 36
20 36 36 36 36 36 36 36
25 36 36 36 36 36 36
32 36 36 36 36 36
40 36 36 36 36
50 36 36 36
63 36 36
S800N – S200P @ 230/400 V
Supply s. S800N
Char. B, C, D
Load s. Icu [kA] 36
In [A] 25 32 40 50 63 80 100 125
S200P B 25 6…16 36 36 36 36 36 36 36 36
20 36 36 36 36 36 36 36
25 36 36 36 36 36 36
15 32 36 36 36 36 36
40 36 36 36 36
50 36 36 36
63 36 36
Supply s. S800N
Char. B, C, D
Load s. Icu [kA] 36
In [A] 25 32 40 50 63 80 100 125
S200P C 25 0.5…16 36 36 36 36 36 36 36 36
20 36 36 36 36 36 36 36
25 36 36 36 36 36 36
15 32 36 36 36 36 36
40 36 36 36 36
50 36 36 36
63 36 36