Page 65 - B_ELSB_Cat_2022_01_MCBs
P. 65
1
1/65
—
MCBs technical details
Coordination tables: back-up
S800N – SN201 @ 230/240 V
Supply s. S800N
Char. B, C, D
Load s. Icu [kA] 36
In [A] 25 32 40 50 63 80 100 125
SN201 B, D 10 6 36 36 36 36 36 36 36 36
10 36 36 36 36 36 36 36 36
16 36 36 36 36 36 36 36 36
20 36 36 36 36 36 36 36
25 36 36 36 36 36 36
32 36 36 36 36 36
40 36 36 36 36
S800N – SN201 @ 230/240 V
Supply s. S800N
Char. B, C, D
Load s. Icu [kA] 36
In [A] 25 32 40 50 63 80 100 125
SN201 C 10 2 36 36 36 36 36 36 36 36
4 36 36 36 36 36 36 36 36
6 36 36 36 36 36 36 36 36
10 36 36 36 36 36 36 36 36
16 36 36 36 36 36 36 36 36
20 36 36 36 36 36 36 36
25 36 36 36 36 36 36
32 36 36 36 36 36
40 36 36 36 36
S800N – SN201L @ 230/240 V
Supply s. S800N
Char. B, C, D
Load s. Icu [kA] 36
In [A] 25 32 40 50 63 80 100 125
SN201 L B, C 6 2 36 36 25 25 18 15 15 15
4 36 36 25 25 18 15 15 15
6 36 36 25 25 18 15 15 15
10 36 36 25 25 18 15 15 15
16 36 36 25 25 18 15 15 15
20 36 25 25 18 15 15 15
25 25 25 18 15 15 15
32 25 18 15 15 15
40 18 15 15 15