Page 67 - B_ELSB_Cat_2022_01_MCBs
P. 67
1
1/67
—
MCBs technical details
Coordination tables: back-up
Supply s. S800C
Char. B, C, D
Load s. Icu [kA] 25
In [A] 25 32 40 50 63 80 100 125
S200 C 10 0.5…6 25 25 25 25 25 25 25 25
8 25 25 25 25 25 25 25 25
10 25 25 25 25 25 25 25 25
13 25 25 25 25 25 25 25 25
16 25 25 25 25 25 25 25 25
20 25 25 25 25 25 25 25
25 25 25 25 25 25 25
32 25 25 25 25 25
40 25 25 25 25
50 25 25 25
63 25 25
S800C – S200M @ 230/400 V
Supply s. S800C
Char. B, C, D
Load s. Icu [kA] 25
In [A] 25 32 40 50 63 80 100 125
S200M B 15 6…16 25 25 25 25 25 25 25 25
20 25 25 25 25 25 25 25
25 25 25 25 25 25 25
32 25 25 25 25 25
40 25 25 25 25
50 25 25 25
63 25 25
Supply s. S800C
Char. B, C, D
Load s. Icu [kA] 25
In [A] 25 32 40 50 63 80 100 125
S200M C 15 0.5…16 25 25 25 25 25 25 25 25
20 25 25 25 25 25 25 25
25 25 25 25 25 25 25
32 25 25 25 25 25
40 25 25 25 25
50 25 25 25
63 25 25