Page 60 - B_ELSB_Cat_2022_01_MCBs
P. 60

1/60             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          Coordination tables: back-up




          S800S – S400M @230/400 V
                           Supply s.        S800S
                   Char.                    B, C, D, K
          Load s.          Icu [kA]         50
                                    In [A]  25       32      40       50      63       80      100      125
          S400M    B, D    Icn [kA]   4*...16  50    50      50       50      50       50      50       50
          S450M            10       20               50      50       50      50       50      50       50
          FS401M
          FS403M                    25                       50       50      50       50      50       50
                                    32                                50      50       50      50       50
                                    40                                        50       50      50       50
                                    50                                                 50      50       50
                                    63                                                         50       50

          * for B characteristic only

                           Supply s.        S800S
                   Char.                    B, C, D, K
          Load s.          Icu [kA]         50
                                    In [A]  25       32      40       50      63       80      100      125
          S400M    C, K    50       0.5...2  50      50      50       50      50       50      50       50
          S450M            25       3...20  50       50      50       50      50       50      50       50
                           15       25                       50       50      50       50      50       50
                                    32                                50      50       50      50       50
                                    40                                        50       50      50       50
                                    50                                                 50      50       50
                                    63                                                         50       50

          S800S – S400M @254/440 V
                           Supply s.        S800S
                   Char.                    B, C, D, K
          Load s.          Icu [kA]         50
                                    In [A]  25       32      40       50      63       80      100      125
          S400M    C. K    15       0.5...2  30      30      30       30      30       30      30       30
          S450M            10       3...10  30       30      30       30      30       30      30       30
                           6        13      30       30      30       30      30       30      30       30
                                    16      30       30      30       30      30       30      30       30
                                    20               30      30       30      30       30      30       30
                                    25                       30       30      30       30      30       30
                                    32                                30      30       30      30       30
                                    40                                        30       30      30       30
                                    50                                                 30      30       30
                                    63                                                         30       30
   55   56   57   58   59   60   61   62   63   64   65