Page 69 - B_ELSB_Cat_2022_01_MCBs
P. 69
1
1/69
—
MCBs technical details
Coordination tables: back-up
S800C – SN201 @ 230/240 V
Supply s. S800C
Char. B, C, D, K
Load.s. Icu [kA] 25
In [A] 25 32 40 50 63 80 100 125
SN201 C 10 2 25 25 25 25 25 25 25 25
4 25 25 25 25 25 25 25 25
6 25 25 25 25 25 25 25 25
10 25 25 25 25 25 25 25 25
16 25 25 25 25 25 25 25 25
20 25 25 25 25 25 25 25
25 25 25 25 25 25 25
32 25 25 25 25 25
40 25 25 25 25
S800C – SN201L @ 230/240 V
Supply s. S800C
Char. B, C, D, K
Load s. Icu [kA] 25
In [A] 25 32 40 50 63 80 100 125
SN201L B, C 6 2 25 25 25 25 18 15 15 15
4 25 25 25 25 18 15 15 15
6 25 25 25 25 18 15 15 15
10 25 25 25 25 18 15 15 15
16 25 25 25 25 18 15 15 15
20 25 25 25 18 15 15 15
25 25 25 18 15 15 15
32 25 18 15 15 15
40 18 15 15 15
S800C – SN201M @ 230/240 V
Supply s. S800C
Char. B, C, D, K
Load s. Icu [kA] 25
In [A] 25 32 40 50 63 80 100 125
SN201M B 10 6 25 25 25 25 25 25 25 25
10 25 25 25 25 25 25 25 25
16 25 25 25 25 25 25 25 25
20 25 25 25 25 25 25 25
25 25 25 25 25 25 25
32 25 25 25 25 25
40 25 25 25 25