Page 72 - B_ELSB_Cat_2022_01_MCBs
P. 72
1/72 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: back-up
S800C – S400M @ 230/400 V
Supply s. S800C
Char. B, C, D
Load s. Icu [kA] 25
In [A] 25 32 40 50 63 80 100 125
S400M B, D Icn [kA] 4*...16 25 25 25 25 25 25 25 25
S450M 10 20 25 25 25 25 25 25 25
25 25 25 25 25 25 25
32 25 25 25 25 25
40 25 25 25 25
50 25 25 25
63 25 25
Supply s. S800C
Char. B, C, D
Load s. Icu [kA] 25
In [A] 25 32 40 50 63 80 100 125
S400M C 25 3...20 25 25 25 25 25 25 25 25
S450M 15 25 25 25 25 25 25 25
32 25 25 25 25 25
40 25 25 25 25
50 25 25 25
63 25 25
Supply s. S800C
Char. B, C, D
Load s. Icu [kA] 25
In [A] 25 32 40 50 63 80 100 125
S400M K 25 3...20 25 25 25 25 25 25 25 25
S450M 10 25 25 25 25 25 25 25
32 25 25 25 25 25
40 25 25 25 25
50 25 25 25
63 25 25