Page 73 - B_ELSB_Cat_2022_01_MCBs
P. 73
1
1/73
—
MCBs technical details
Coordination tables: back-up
S800B – S200 @ 230/400 V
Supply s. S800B
Char. B, C, D, K
Load s. Icu [kA]
In [A] 32 40 50 63 80 100 125*
S200 B 10 6 16 16 16 16 16 16 16
10 16 16 16 16 16 16 16
13 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16
20 16 16 16 16 16 16 16
25 16 16 16 16 16 16
32 16 16 16 16 16
40 16 16 16 16
50 16 16 16
63 16 16 16
Supply s. S800B
Char. B, C, D, K
Load s. Icu [kA]
In [A] 32 40 50 63 80 100 125*
S200 C, D, K, Z 10 0.5…6 16 16 16 16 16 16 16
8 16 16 16 16 16 16 16
10 16 16 16 16 16 16 16
13 16 16 16 16 16 16 16
16 16 16 16 16 16 16 16
20 16 16 16 16 16 16 16
25 16 16 16 16 16 16
32 16 16 16 16 16
40 16 16 16 16
50 16 16 16
63 16 16 16
* only S800B-B,C
back-up values indicated in kA