Page 84 - B_ELSB_Cat_2022_01_MCBs
P. 84
1/84 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: back-up
Fuse - S300P @ 415V AC
Supply s. NH 00
gG
Iu [A] 100
Load s. Char. Icu [kA]
ln [A] 20 25 35 40 63 80 100 125 160 200
6 100 100 100 100 100 50 50 50 45
10 100 100 100 100 100 50 50 50 45
13...16 100 100 100 100 100 50 50 50 35
S300P B 25 20 100 100 100 100 100 100 50 50 30
25 100 100 100 100 100 100 100 50 30
32...40 100 100 100 100 100 100 100 100 30 50
50...63 100 100 100 100 100 100 100 100 100 50
Fuse - S300P @ 415V AC
Supply s. NH 00
gG
Iu [A] 100
Load s. Char. Icu [kA]
ln [A] 20 25 35 40 63 80 100 125 160 200
3...4 100 100 100 100 50 50 50 50
6...8 100 100 100 100 100 50 50 50 45
10 100 100 100 100 100 50 50 50 45
S300P C 25 13...16 100 100 100 100 100 100 50 50 35
20...25 100 100 100 100 100 100 100 50 30
32...40 100 100 100 100 100 100 100 100 30 50
50...63 100 100 100 100 100 100 100 100 100 50
Fuse - S300P @ 415V AC
Supply s. NH 00
gG
Iu [A] 100
Load s. Char. Icu [kA]
ln [A] 20 25 35 40 63 80 100 125 160 200
3 100 100
4 100 100 100
6 100 100 100 100 100
8...10 100 100 100 100 100 100 50 45 45
S300P D 25
13...16 100 100 100 100 100 100 45 40 35
20 100 100 100 100 100 100 100 35 30
25 100 100 100 100 100 100 100 100 30
32...63 100 100 100 100 100 100 100 100 100 50
Fuse - S300P @ 415V AC
Supply s. NH 00
gG
Iu [A] 100
Load s. Char. Icu [kA]
ln [A] 20 25 35 40 63 80 100 125 160 200
3 100 100
4 100 100 100
6 100 100 100 100 100
8...10 100 100 100 100 100 100 50 45 45
S300P K 25
13...16 100 100 100 100 100 100 45 40 35
20 100 100 100 100 100 100 100 35 30
25 100 100 100 100 100 100 100 100 30
32...63 100 100 100 100 100 100 100 100 100 50