Page 81 - B_ELSB_Cat_2022_01_MCBs
P. 81
1
1/81
—
MCBs technical details
Coordination tables: back-up
S800U – S400M @230/400 V
Supply s. S800U
Char. K, Z
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
S400M B, D Icn [kA] 4*...16 50 50 50 50 50 50 50 50
S450M 10 20 50 50 50 50 50 50 50
25 50 50 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50
50 50 50 50
63 50 50
Supply s. S800U
Char. K, Z
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
S400M C 25 3...20 50 50 50 50 50 50 50 50
S450M 15 25 50 50 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50
50 50 50 50
63 50 50
Supply s. S800U
Char. K, Z
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
S400M K 25 3...20 50 50 50 50 50 50 50 50
S450M 10 25 50 50 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50
50 50 50 50
63 50 50