1/80 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: back-up
Supply s. S800U
Char. K, Z
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
S200P C 25 0.5...16 50 50 50 50 50 50 50 50
20 50 50 50 50 50 50 50
25 50 50 50 50 50 50
15 32 50 50 50 50 50
40 50 50 50 50
50 50 50 50
63 50 50
S800U – S400E @230/400 V
Supply s. S800U
Char. K, Z
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
S400E B Icn [kA] 6 50 50 50 50 50 50 50 50
6 10 50 50 50 50 50 50 50 50
13 50 50 50 50 50 50 50 50
16 50 50 50 50 50 50 50 50
20 50 50 50 50 50 50 50
25 50 50 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50
50 50 50 50
63 50 50
Supply s. S800U
Char. K, Z
Load s. Icu [kA] 50
In [A] 25 32 40 50 63 80 100 125
S400E C Icn [kA] 0.5...6 50 50 50 50 50 50 50 50
6 10 50 50 50 50 50 50 50 50
13 50 50 50 50 50 50 50 50
16 50 50 50 50 50 50 50 50
20 50 50 50 50 50 50 50
25 50 50 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50
50 50 50 50
63 50 50