Page 190 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 190
The requirements for the inner zones must be defined accord- ary is formed by the shielding measures. The implementation
ing to the dielectric strength of the electrical and electronic of the lightning protection zone concept is an important pre-
systems to be protected. requisite for safe and undisturbed operation.
Equipotential bonding must be established at the boundary of To ensure the required availability of the installation, a lot of
each inner zone for all incoming metal parts and supply lines information (e.g. on the use of the building, earth-termination
either directly or by means of suitable SPDs. The zone bound- system, electrical installation, computer system) must be col-
LPZ 0 A LPZ 0 A
LPZ 0 B LPZ 0 B
LPZ 2 LPZ 2
LPZ 2 LPZ 1 LPZ 2 LPZ 1
LPZ 0 B
LPZ 3
LPZ 2 LPZ 1 LPZ 2
LPZ 1 LPZ 1
LPZ 2 LPZ 2
MEB MEB
Figure 7.1.2b Lightning protection zone concept according to IEC 62305-4 (EN 62305-4)
www.dehn-international.com LIGHTNING PROTECTION GUIDE 189