Page 273 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 273

radius of the
                                                          rolling sphere



           radius of the
           rolling sphere








          Application     Type              Part No.    Application     Type              Part No.
          Lightning current arresters                   Lightning current arresters
          TN system       DB M 1 255 (2x)    961 120    TN-S system     DB M 1 255 (4x)   961 120
                          DB M 1 255         961 120                    DB M 1 255 (3x)   961 120
          TT system                                     TT system
                          DGP M 1 255        961 101                    DGP M 1 255       961 101
          Combined arresters                            Combined arresters
          TN system       DSH TN 255         941 200    TN-S system     DSH TNS 255       941 400
          TT system       DSH TT 2P 255      941 110    TT system       DSH TT 255        941 310
          Figure 9.2.3  Outdoor lighting system in the form of a 230 V wall   Figure 9.2.4  Outdoor lighting system in the form of a 3x 230/400 V
                  lamp in lightning protection zone 0 A  with lightning   lamp pole in lightning protection zone 0 A  with light-
                  equipotential bonding at the entrance point into the   ning equipotential bonding at the entrance point into
                  building                                      the building

          The  recommended  arrester  types  must  be  installed  at  the
          transition from LPZ 0 A  to 1 or from LPZ 0 B  to 1.
          Type 1 lightning current arresters must be provided at the
          entrance point into the building for all outdoor lighting sys-
          tems in LPZ 0 A . To determine this lightning protection zone,
          the relevant rolling sphere is “rolled over” the outdoor light-            radius of the
          ing system from all possible directions. If the rolling sphere              rolling sphere
          touches the outdoor lighting system, it is located in LPZ 0 A
          (Figures 9.2.3 and 9.2.4).

          Before installing type 1 lightning current arresters, it has to be
          checked whether an energy-coordinated type 2 surge arrester
          is already installed in the distribution board which houses the
          circuits of the outdoor lighting system. If this is not the case,
          we recommend to install combined arresters at the transition
          of the lightning protection zones.
          Type 2 surge arresters must also be installed at the entrance   Application  Type  Part No.
          point  into  the  building  for  all  outdoor  lighting  systems  in     TN system  DG M TN 275  952 200
          LPZ 0 B  (Figure 9.2.5).
                                                        TT system       DG M TT 2P 275    952 110
                                                       Figure 9.2.5  Outdoor lighting system in the form of a 230 V wall
                                                                lamp in lightning protection zone 0 B



          272  LIGHTNING PROTECTION GUIDE                            www.dehn-international.com
   268   269   270   271   272   273   274   275   276   277   278