Page 294 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 294

≥ 2 m
                                                                                  protective angle





                                                                                 s







                                                                                   2
                                                                                4 mm  Cu
              4 mm 2  Cu     max. 1.5 m

       Figure 9.5.4  Arrangement of antennas which do not have to be   Figure 9.5.5  Antenna system located in the protected volume of an
               earthed                                       existing air-termination system


       Building with lightning protection system    described before, in all these cases, the lowest point of the
       The following considerations have been made in conformity   cable shields must be connected to the main earthing busbar
       with the protection goal of the IEC 62305-3 (EN 62305-3) light-  via copper equipotential bonding conductors with a minimum
                                                                    2
       ning protection standard and the so-called “best solution(s)”   cross-section of 4 mm  to reduce the risk of induction loops
       of the antenna standard.                     (Figure 9.5.3).
       If buildings are equipped with a lightning protection system,
       the antenna system must be positioned in the protected vol-  Building without lightning protection system
       ume of an existing air-termination system (Figure 9.5.5) or   Earthing measures for antennas do not ensure preventive
       protected by an air-termination rod isolated by a DEHNiso   lightning protection for buildings or any other structures.
       spacer (Figure 9.5.6) or by a DEHNcon-H solution (Figure   If buildings are not equipped with a lightning protection sys-
       9.5.7). In addition to establishing equipotential  bonding as   tem, the antenna mast must be earthed. The earthing conduc-


                         protective angle             DEHNcon-H*                  protective angle
                                                      e.g. Part No. 819 250
                                                      (observe installation instructions)
                      GRP spacers
                                       s







         DEHNiso spacer
         e.g. with pipe clamp
         Part No. 106 225    4 mm  Cu                               4 mm  Cu
                                                                       2
                                 2
       Figure 9.5.6  Antenna system with an air-termination rod isolated by   Figure 9.5.7  Antenna system with high-voltage-resistant, insulated
               DEHNiso spacers (insulating clearance made of glass-  down conductor DEHNcon-H
               fibre reinforced plastic (GRP))



            www.dehn-international.com                             LIGHTNING PROTECTION GUIDE  293
   289   290   291   292   293   294   295   296   297   298   299