Figure 9.4.5  DEHNventil installed in a switchgear cabinet for pro-  Figure 9.4.6  DEHNconnect terminal blocks with integrated surge
               tecting the power supply systems              protection for protecting the complete measuring and
                                                             control equipment

       applications (for more detailed information, please also see
       brochure DS 649 E “Red/Line Selection Guide”).

       Surge protection for information technology systems
       The entrance point into the building serves as a transfer point
       between all information technology lines and the sewage
       plant. At this point, lightning current carrying SPDs (category
       D1), e.g. of type DRL 10 B 180 FSD, are installed. The lines
       are directly routed from this transfer point to the switch-
       gear cabinets and are connected there. According to the risk
       analysis,  the  incoming  lines  for  the  20  mA  signals  and  the
       telecontrol system must be protected by adequate arresters
       from the DEHNconnect or BLITZDUCTOR series. These SPDs can
       be installed in conformity with the lightning protection zone
       concept  (category  C2)  and  are  compatible  with  the  system
       (Figures 9.4.6 and 9.4.7).
       This ensures a consistent surge protection concept for the in-
       formation technology lines.
       Additional applications for protecting sewage plants can be   Figure 9.4.7  DEHNconnect surge protection devices; lines entering
       found in brochure DS 107 E which can be downloaded at   from the double floor
       www.dehn-international.com.