MEB






              DNO



                   Telecontrol /
                   telecommunication

              Ex i  Measuring and control equipment

              PROFI
              BUS

                              heater



              gas



                                       foundation earth electrode                    external LPS

          No. in Fig. Protection for           Surge protective device    *floating remote signalling contact  Part No.
          Power supply systems
                                               DEHNventil DV M TNC 255                     951 300
                    TN-C system                DEHNventil DV M TNC 255 FM*                 951 305
                                               DEHNventil DV ZP TNC 255                    900 390
                                               DEHNventil DV M TT 255                      951 310
                    TN-S/TT system             DEHNventil DV M TT 255 FM*                  951 315
                                               DEHNventil DV ZP TT 255                     900 391
          Information technology systems
                                               BLITZDUCTOR BXT ML2 BD 180 or               920 247
                    Telecontrol, telecommunication  BLITZDUCTOR BXT ML4 BD 180             920 347
                                               + BXT BAS base part                       + 920 300
          Measuring and control equipment
                                               BLITZDUCTOR BXT ML2 BD S EX 24 or           920 280
                    Intrinsically safe measuring circuits   BLITZDUCTOR BXT ML4 BD EX 24   920 381
                    + systems
                                               + BXT BAS base part                       + 920 301
          Bus systems
                                               BLITZDUCTOR BXT ML2 BD HFS 5                920 271
                    e.g. Profibus DP
                                               + BXT BAS base part                       + 920 300
          Figure 9.4.4  Lightning equipotential bonding according to DIN EN 62305-3 (VDE 0185-305-3), Supplement 1



          288  LIGHTNING PROTECTION GUIDE                            www.dehn-international.com