Page 469 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 469

Figure 8.1.5.2c  IT system with incorporated neutral conductor; “3+1”    Figure 8.2.6   Sparkover performance of a gas discharge tube at
                   circuit.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 233  du/dt = 1 kV/µs.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 246
          Figure 8.1.5.3   SPDs used in a 690 V IT system – Without incorporated    Figure 8.2.7   Test setup for determining the limiting voltage in case of
                   neutral conductor.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 233  nominal discharge currents.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 247
          Figure 8.1.5.4   SPDs used in a 230/400 V IT system – With incorporated   Figure 8.2.8   Limiting voltage in case of nominal discharge currents   .  . 247
                   neutral conductor (3+1 circuit) .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 234  Figure 8.2.9   Nominal current of BLITZDUCTOR XT.  .  .  .  .  .  .  .  .  .  .  . 247
         Figure 8.1.6.1   Surge protective devices connected in series .  .  .  .  .  .  .  . 235  Figure 8.2.10   Typical frequency response of a BLITZDUCTOR XT  .  .  .  .  . 247
         Figure 8.1.6.2   Principle of the two-conductor terminal (single-pole unit)  . 235
                                                       Figure 8.2.11   Building with external lightning protection system and
         Figure 8.1.6.3   STAK 2X16 and STAK 25 pin-shaped terminals.  .  .  .  .  .  . 235  cables installed outside the building according to the
         Figure 8.1.6.4a  Connection of surge pro tective devices in the cable branch  235  lightning protection zone concept  .  .  .  .  .  .  .  .  .  .  .  .  . 248
          Figure 8.1.6.4b  Limiting voltage of DEHNguard 275 in case of different    Figure 8.2.12   Building without external lightning protection system
                   connecting cable lengths .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 235  and cables installed outside the building.  .  .  .  .  .  .  .  .  . 248
          Figure 8.1.6.5   DEHNbloc Maxi S: Coordinated lightning current arrester    Figure 8.2.13   Building with external lightning protection system and
                   with integrated backup fuse for busbars .  .  .  .  .  .  .  .  .  . 236  cables installed inside the building according to the
          Figure 8.1.6.6   DEHNguard modular CI: Type 2 surge arrester with    lightning protection zone concept  .  .  .  .  .  .  .  .  .  .  .  .  . 248
                   integrated backup fuse .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 236  Figure 8.2.14   Building without external lightning protection system
          Figure 8.1.6.7   Recommended maximum cable lengths of surge    and cables installed inside the building   .  .  .  .  .  .  .  .  .  . 248
                   protective devices in the cable branch (IEC 60364-5-53    Figure 8.2.15   Block diagram for the temperature measurement  .  .  .  .  . 250
                   (HD 60364-5-534))   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 236
                                                       Figure 8.2.1.1   Optocoupler – Schematic diagram  .  .  .  .  .  .  .  .  .  .  .  .  . 252
          Figure 8.1.6.8a  Unfavourable cable routing from the consumer’s point    Figure 8.2.2.1   Levels of building automation  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 253
                   of view  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 236
                                                       Figure 8.2.3.1   Generic cabling structure.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 254
          Figure 8.1.6.8b  Favourable cable routing from the consumer’s point of
                   view  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 236  Figure 8.2.3.2   Lightning interference on the IT cabling  .  .  .  .  .  .  .  .  .  . 255
         Figure 8.1.6.9   Arrangement of surge protective devices in an installation    Figure 8.2.4.1   Calculation of L 0  and C 0   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 257
                   and the resulting effective cable length  .  .  .  .  .  .  .  .  .  . 237  Figure 8.2.4.2   Intrinsically safe BXT ML4 BD EX 24 arrester.  .  .  .  .  .  .  . 258
          Figure 8.1.6.10  Series connection.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 238  Figure 8.2.4.3   SPDs in intrinsically safe bus systems – Insulation
          Figure 8.1.6.11  Series connection of the DEHNventil M TNC combined    strength > 500 V a.c. .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 259
                   arrester by means of a busbar  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 238  Figure 8.2.5.1   Correct installation .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 260
          Figure 8.1.6.12  Parallel connection  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 238  Figure 8.2.5.2   Most common installation  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 260
          Figure 8.1.6.13  Cable routing .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 239  Figure 8.2.5.3   Incorrectly established equipotential bonding  .  .  .  .  .  .  . 261
         Figure 8.1.7.1   One-port SPD .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 239  Figure 8.2.5.4   Incorrect conductor routing.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 261
         Figure 8.1.7.2   Two-port SPD.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 239  Figure 8.2.5.5   Separation of cables in cable duct systems.  .  .  .  .  .  .  .  . 262
         Figure 8.1.7.3   Through-wired one-port SPD   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 239  Figure 8.2.6.1   Ageing of electronic components – “Bath tub curve”  .  .  . 263
         Figure 8.1.7.4   Example: DEHNventil M TNC 255.  .  .  .  .  .  .  .  .  .  .  .  .  . 240  Figure 8.2.6.2   LifeCheck arrester testing by means of DRC LC M1+   .  .  . 263
         Figure 8.1.7.5   Example: DEHNguard M TNC/TNS/TT.  .  .  .  .  .  .  .  .  .  .  . 240  Figure 8.2.6.3   Monitoring of surge protective devices by means of the
         Figure 8.1.7.6   Example: DEHNrail  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 241  DRC MCM XT condition monitoring unit  .  .  .  .  .  .  .  .  .  . 264
         Figure 8.1.7.7   Performance of NH fuses when subjected to impulse    Figure 9.1.1   Basic principle of a frequency converter  .  .  .  .  .  .  .  .  .  . 267
                   currents (10/350 µs)  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 241  Figure 9.1.2   EMC-compatible shield connection of the motor feeder
         Figure 8.1.7.8   Current and voltage of a melting 25 A NH fuse when    cable  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 267
                   subjected to impulse currents (10/350 µs)  .  .  .  .  .  .  .  .  . 241
         Figure 8.1.7.9   Use of a separate backup fuse for surge protective devices  . 241  Figure 9.1.3   Frequency converter with drives in LPZ 0 A  and LPZ 1.  .  .  . 268
                                                       Figure 9.2.1   Standing surface insulation to reduce the risk of touch
          Figure 8.1.7.10  Reduction of the follow current by means of the patented   voltage in case of a lightning strike to a lamp pole.  .  .  .  . 271
                   RADAX Flow principle  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 242
                                                       Figure 9.2.2   Potential control to reduce step voltage in case of a
          Figure 8.1.7.11  Follow current disconnection selectivity of DEHNventil M    lightning strike to a lamp pole  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 271
                   with respect to NH fuse links with different rated currents  . 242
                                                       Figure 9.2.3   Outdoor lighting system in the form of a 230 V wall lamp
          Figure 8.1.8.1   DEHNguard M TNC CI 275 FM – Type 2 arrester with    in lightning protection zone 0 A  with lightning equipoten-
                   integrated backup fuse .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 243
                                                                tial bonding at the entrance point into the building  .  .  .  . 272
          Figure 8.1.8.2   Inner structure of the DEHNguard M/S … CI (front and    Figure 9.2.4   Outdoor lighting system in the form of a 3x 230/400 V
                   rear view).  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 243
                                                                lamp pole in lightning protection zone 0 A  with lightning
          Figure 8.1.8.3   Considerably reduced space requirements – Com parison    equipotential bonding at the entrance point into the
                   of the installation space of a conventional type 1 arrester    building.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 272
                   with that of DEHNvenCI  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 243
                                                       Figure 9.2.5   Outdoor lighting system in the form of a 230 V wall lamp
         Figure 8.2.1   SPD classification.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 244  in lightning protection zone 0 B .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 272
         Figure 8.2.2   Limiting performance.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 245  Figure 9.3.1   System overview of a biogas plant .  .  .  .  .  .  .  .  .  .  .  .  . 275
         Figure 8.2.3   Special applications   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 245  Figure 9.3.2   DEHNiso Combi system used to protect a fermenter with
         Figure 8.2.4   Nominal voltage and reference.  .  .  .  .  .  .  .  .  .  .  .  .  .  . 245  foil roof.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 276
         Figure 8.2.5   Test setup for determining the limiting voltage at a rate    Figure 9.3.3   Protection of a fermenter with a foil roof by means of
                   of voltage rise du/dt = 1 kV/µs  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 246  telescopic lightning protection masts.  .  .  .  .  .  .  .  .  .  .  . 277

          468  LIGHTNING PROTECTION GUIDE                            www.dehn-international.com
   464   465   466   467   468   469   470   471   472   473   474