Page 35 - ACB-E1.2-E2.2-E4.2-E6.2
P. 35

CE Ema
                                                                                                                x 2
                                                                                                    ABB | SACE Emax 2
                                                                                                    ABB | SA
       4 - Voltage Advanced protections

       List
       The Advanced Voltage protections, available by default for the Ekip G Touch and Ekip G Hi-Touch models and configurable in the remaining
       models as additional SW package, are:
       Name        Type of protection                  Threshold   Time        Additional functions  (3)
       S(V)        Short-circuit with voltammetric control                     Mode, Trip enable, Block
       S2(V)  (1)  Short-circuit with voltammetric control                     Mode, Trip enable, Block
       RV  (2)     Residual voltage                                            Trip enable, Block

       Further details about the protections are given in document 1SDH001330R1002.

       (1)  S2(V) protection is not available by default with Ekip G Touch. However, it can be integrated by requesting the relative SW package
       (2)  available for 4P or 3P circuit-breakers configured with external neutral voltage
       (3)  Block configuration available via Ekip Connect

       Summary table
                                                                       Calculation
            ANSI                               Tolerance
       ABB         Threshold  (7)(8)                     Time          formula t  Tolerance t   (5)
            (6)                                threshold                 (4)                 t
                                                                       t
                   I20 = 0,6...10 In step = 0,1 In ;                              The best of the two values: ± 10% or ±
                                         (9)
                   Ul = 0,2...1 Un step = 0,01 Un ;     t20 = 0,05...30 s
                                          (9)
       S(V)  51V                               ± 10 %                  t  = t20   40 ms (for set time < 5 s) / ±  100 ms
                   Uh = 0,2...1 Un step = 0,01 Un ;     Step = 0,01 s    t        (for set time ≥ 5 s)
                                           (9)
                   Ks = 0,1…1 step = 0,01  (9)
                   I21 = 0,6...10 In step = 0,1 In  (10) ;                        The best of the two values: ± 10% or ±
                   Ul2 = 0,2...1 Un step = 0,01 Un  (10) ;  t21 = 0,05...30 s
       S2(V) 51V                               ± 10 %                  t  = t21   40 ms (for set time < 5 s) / ±  100 ms
                   Uh2 = 0,2...1 Un step = 0,01 Un  (10) ;  Step = 0,01 s   t
                   Ks2 = 0,1…1; step = 0,01  (10)                                 (for set time ≥ 5 s)
                                                                                  The best of the two values: ± 10% or ±
                   U22 = 0,05...0,5 Un Step = 0,001     t22 = 0,05...120 s
       RV   59N                                ± 5 %  (11)             t  = t22   40 ms (for set time < 5 s) / ±  100 ms
                   Un                                   Step = 0,01 s    t
                                                                                  (for set time ≥ 5 s)
       (4)  calculation of t  is valid for values which have exceeded the trip threshold of the protection
                     t
       (5)  tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values
       within operating limits; the tolerance value is ± 20% if the conditions are not guaranteed
       (6)  ANSI / IEEE C37-2 codification
       (7)  S(V) protection: in the Linear mode, the current trip threshold for voltage values between Ul and Uh is calculated by performing linear
       interpolation between thresholds Uh and I20 (first point of the line) and Ul and Ks * I20 (second point of the line). I   = [I20 * (1 - Ks) *
                                                                                                 threshold
       (U      - Uh)] / (Uh - Ul) + I20
         measured
       (8)  S2(V) protection: in the Linear mode, the current trip threshold for voltage values between Ul2 and Uh2 is calculated by performing
       linear interpolation between thresholds Uh2 and I21 (first point of the line) and Ul2 and Ks2 * I21 (second point of the line). I   = [I21 *
                                                                                                       threshold
       (1 - Ks2) * (U   – Uh2)] / (Uh2 - Ul2) + I21
                 measured
       (9)  the threshold Ks setting must ensure the following limitation: Ks * I20 ≥ 0.6 In; parameter Uh is available in the Linear mode; the setting
       must comply with the following limitation: Uh > Ul
       (10)  the threshold Ks2 setting must ensure the following limitation: Ks2 * I21 ≥ 0.6 In; parameter Uh2 is available in the Linear mode; the
       setting must comply with the following limitation: Uh2 > Ul2
       (11) tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current
       values within operating limits; the tolerance value is ± 10% if the conditions are not guaranteed





















       33 | © 2022 ABB |  1SDH001316R1002 - ECN000232533                                                  Protections