Page 36 - ACB-E1.2-E2.2-E4.2-E6.2
P. 36

ABB | SACE Emax 2
                                                                                                    ABB | SA CE Ema x 2
       5 - Frequency protections

       List
       The Frequency protections, available by default for Ekip Hi-Touch, Ekip G Touch, Ekip G-Hi Touch models and configurable in the remaining
       models as additional SW package, are:
       Name        Type of protection                  Threshold   Time        Additional functions  (2)
       UF          Minimum frequency                                           Trip enable, Block
       OF          Maximum frequency                                           Trip enable, Block
       UF2  (1)    Minimum frequency                                           Trip enable, Block
       OF2  (1)    Maximum frequency                                           Trip enable, Block

       Further details about the protections are given in document 1SDH001330R1002.

       (1)  protections UF2 and OF2 are not available by default with Ekip G Touch. However, they can be integrated by requesting the relative SW
       package
       (2)  Block configuration available via Ekip Connect

       Summary table
                                                            Calculation
                                   Tolerance
       ABB   ANSI  (5)  Threshold  (7)(8)    Time           formula t  Tolerance t   (4)
                                   threshold                  (3)                 t
                                                            t
                                                                       The best of the two values: ± 10 % (min = 30 ms) or ±
                     f12 = 0,9...1 fn        t12 = 0,06...300 s
       UF  (6)  81L                ± 1 %  (7)               t  = t12   40 ms (for set time < 5 s) / ±  100 ms (for set time ≥ 5
                     Step = 0,001 fn         Step = 0,01 s    t
                                                                       s)
                     f13 = 1...1,1 fn        t13 = 0,06...300 s        The best of the two values: ± 10% or ±  40 ms (for set
       OF  (6)  81H                ± 1 %  (7)               t  = t13
                     Step = 0,001 fn         Step = 0,01 s    t        time < 5 s) / ±  100 ms (for set time ≥ 5 s)
                                                                       The best of the two values: ± 10 % (min = 30 ms) or ±
                     f17 = 0,9...1 fn        t17 = 0,06...300 s
       UF2  (6)  81L               ± 1 %  (7)               t  = t17   40 ms (for set time < 5 s) / ±  100 ms (for set time ≥ 5
                     Step = 0,001 fn         Step = 0,01 s    t
                                                                       s)
                     f18 = 1...1,1 fn        t18 = 0,06...300 s        The best of the two values: ± 10% or ±  40 ms (for set
       OF2  (6)  81H               ± 1 %  (7)               t  = t18
                     Step = 0,001 fn         Step = 0,01 s    t        time < 5 s) / ±  100 ms (for set time ≥ 5 s)
       (3)  calculation of t  is valid for values which have exceeded the trip threshold of the protection
                     t
       (4)  tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values
       within operating limits; the tolerance value is ± 20% if the conditions are not guaranteed
       (5)  ANSI / IEEE C37-2 codification
       (6)  the protection excludes itself if the maximum value of the line-to-line voltage is less than 32 V with hysteresis at 36 V
       (7)  tolerance valid for frequencies within range: fn ± 2%; a ± 5% tolerance is available for off range frequencies