       Continued from the previous page                                                             ABB | SACE Emax 2

       Summary table of additional functions in conjunction with protections D and UP:
                                                   Tolerance                         Calculation
       ABB          ANSI  (7)  Threshold                      Time                               Tolerance t   (6)
                                                   threshold                         formula t   (5)       t
                                                                                              t
                                                              t23startup= 0,1...30 s,  step
       UP (Startup)  (10)
                                                              = 0,01 s
                                                                                                 The better of the two
                            I7startup Fw/Bw = 0,6...10        t7startup = 0,1...30 s step =
       D (Startup)                                 ± 10 %                            tt = t7startup values: ± 10 % or ±
                            In step = 0,1 In                  0,01 s
                                                                                                 40 ms
                                                              t7SdZ Fw/Bw = 0,1...0,8 s
       D (SdZ)      68      -                      -
                                                              step = 0,01 s
       (10)  UP protection startup should be considered as the temporary deactivation time of the protection, from the point in which the startup
       threshold is exceeded





       7 - ROCOF protections


       Description
       The ROCOF Protection package includes the protection of the same name and is available by default for Ekip G Hi-Touch; it can be configured in
       the remaining models as additional SW package
       ROCOF Protection protects against rapid frequency variations and has the following additional functions: Trip Enable, Trip Direction and Block.
       Further details about the protections are given in document 1SDH001330R1002.

       Summary table
                                            Tolerance                                Calculation
       ABB          ANSI  (3)  Threshold               Time                                      Tolerance t   (2)
                                            threshold                                formula t   (1)       t
                                                                                              t
                                                                                                 The best of the two
                            f28 = 0,4...10 Hz / s
       ROCOF  (4)   81R                     ± 10 %  (5)  t28 = 0,06...300 s step = 0,01 s  t  = t28  values: ± 20% or 200
                            step = 0,2 Hz / s                                         t
                                                                                                 ms
       (1)  calculation of t  is valid for values which have exceeded the trip threshold of the protection
                     t
       (2)  tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values
       within operating limits; the tolerance value becomes ± 20% if the conditions are not guaranteed
       (3)  ANSI / IEEE C37-2 codification
       (4)  not active for voltage values < 30 V
       (5)  ± 20% for threshold 0.4 Hz / s





       8 - Adaptive protections

       Description
       The Adaptive Protection package includes the Double Set protection and is available by default for Ekip G Hi-Touch; it can be configured in the
       remaining models as additional SW package
       The Double Set function enables two different protection configurations to be made, one as an alternative to the other, by means of a set change
       with programmable events.

       Parameters
       The function can be activated and the Set of the main protections configured in the Settings - Double Set menu; the event that determines Set
       change (from main to secondary) can be programmed in the Advanced - Functions menu.