6 - Power protections
List
The Power protections, available by default for Ekip Hi-Touch, Ekip G Touch, Ekip G-Hi Touch models and configurable in Ekip Touch as additional
SW package, are:
Name Type of protection Threshold Time Additional functions (3)
RP Reverse active power Trip enable, Block
Trip enable, Directional Zone Selectivity ,
(4)
D (2) Directional short-circuit with adjustable delay
Startup enable, Block, Direction Min Angle
OQ (1) Maximum reactive power Trip enable, Block
OP (1) Active overpower Trip enable, Block
UP (1) Active underpower Trip enable, Block, Startup enable
RQ (1)(2) Reverse reactive power Trip enable, Block
Cos φ Minimum Cos φ
Further details about the protections are given in document 1SDH001330R1002.
(1) the protection is not available by default with Ekip Hi-Touch. However, it can be integrated by requesting the relative SW package
(2) the protection is not available by default with Ekip G Touch. However, it can be integrated by requesting the relative SW package
(3) Block configuration available via Ekip Connect
(4) Directional Zone Selectivity functions as an alternative to Zone Selectivity S and G
WARNING! The Power flow parameters effect the sign of the power and power factor values measured by the unit. Power flow
must be configured and verified on the basis of your installation to ensure that all the protections of the Power Protections
package function correctly
Summary table
Calculation
Tolerance
ABB ANSI (7) Threshold Time formula t Tolerance t (6)
threshold (5) t
t
The best of the two values: ± 10% or ±
P11 = -1...-0,05 Sn step = t11 = 0,5...120 s
RP 32R ± 10 % t = t11 40 ms (for set time < 5 s) / ± 100 ms (for
0,001 Sn step = 0,01 s t
set time ≥ 5 s)
t7 Fw/Bw = ± 40 ms (for t7 ≥ 400 ms) / whichever is
I7 Fw/Bw = 0,6...10 In step ± 7 % If ≤ 6 In
D (8) 67 0,1...0,8 s step = t = t7 higher, ± 20 ms or ± 10 % (for t7 < 400
= 0,1 In ± 10 % If > 6 In t
0,01 s ms)
The best of the two values: ± 10% or ±
Q27 = 0,4...2 Sn step = t27 = 0,5...100 s
OQ 32OF ± 10 % t = t27 40 ms (for set time < 5 s) / ± 100 ms (for
0,001 Sn step = 0,5 s t
set time ≥ 5 s)
The best of the two values: ± 10% or ±
P26 = 0,4...2 Sn step = t26 = 0,5...100 s
OP 32OF ± 10 % t = t26 40 ms (for set time < 5 s) / ± 100 ms (for
0,001 Sn step = 0,5 s t
set time ≥ 5 s)
The best of the two values: ± 10% or ±
P23 = 0,1...1 Sn step = t23 = 0,5...100 s
UP (9) 32LF ± 10 % t = t23 40 ms (for set time < 5 s) / ± 100 ms (for
0,001 Sn step = 0,5 s t
set time ≥ 5 s)
Q24 = -1...-0,1 Sn step =
0,001 Sn; Kq = -2…2 step t24 = 0,5...100 s The best of the two values: ± 10% or ±
RQ 40 / 32R ± 10 % t = t24 40 ms (for set time < 5 s) / ± 100 ms (for
= 0,01; Vmin = 0,5...1,2 Un step = 0,5 s t set time ≥ 5 s)
step = 0,01
Cos φ 78 Cos φ = 0,5...0,95 step =
0,01
(5) calculation of t is valid for values which have exceeded the trip threshold of the protection
t
(6) tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values
within operating limits; the tolerance value is ± 20% if the conditions are not guaranteed
(7) ANSI / IEEE C37-2 codification
(8) the protection does not detect the fault current direction for < 5 V voltages.
(9) not active if the circuit-breaker is open (TRIP OFF is signaled); the protection is also active for negative active power, but is independent
of RP protection (Protection from inverse active power)
Continued on the next page
35 | © 2022 ABB | 1SDH001316R1002 - ECN000232533 Protections