Page 37 - ACB-E1.2-E2.2-E4.2-E6.2
P. 37

ABB | SACE Emax 2
                                                                                                    ABB | SA CE Ema x 2
       6 - Power protections

       List
       The Power protections, available by default for Ekip Hi-Touch, Ekip G Touch, Ekip G-Hi Touch models and configurable in Ekip Touch as additional
       SW package, are:
       Name       Type of protection                  Threshold  Time       Additional functions  (3)
       RP         Reverse active power                                      Trip enable, Block
                                                                            Trip enable, Directional Zone Selectivity ,
                                                                                                            (4)
       D  (2)     Directional short-circuit with adjustable delay
                                                                            Startup enable, Block, Direction Min Angle
       OQ  (1)    Maximum reactive power                                    Trip enable, Block
       OP  (1)    Active overpower                                          Trip enable, Block
       UP  (1)    Active underpower                                         Trip enable, Block, Startup enable
       RQ  (1)(2)  Reverse reactive power                                   Trip enable, Block
       Cos φ      Minimum Cos φ

       Further details about the protections are given in document 1SDH001330R1002.

       (1)  the protection is not available by default with Ekip Hi-Touch. However, it can be integrated by requesting the relative SW package
       (2)  the protection is not available by default with Ekip G Touch. However, it can be integrated by requesting the relative SW package
       (3)  Block configuration available via Ekip Connect
       (4)  Directional Zone Selectivity functions as an alternative to Zone Selectivity S and G


             WARNING! The Power flow parameters effect the sign of the power and power factor values measured by the unit. Power flow
             must be configured and verified on the basis of your installation to ensure that all the protections of the Power Protections
             package function correctly
       Summary table
                                                                       Calculation
                                           Tolerance
       ABB    ANSI  (7)  Threshold                       Time          formula t  Tolerance t   (6)
                                           threshold                     (5)                t
                                                                       t
                                                                                  The best of the two values: ± 10% or ±
                      P11 = -1...-0,05 Sn step =         t11 = 0,5...120 s
       RP     32R                          ± 10 %                      t  = t11   40 ms (for set time < 5 s) / ±  100 ms (for
                      0,001 Sn                           step = 0,01 s   t
                                                                                  set time ≥ 5 s)
                                                         t7 Fw/Bw =               ± 40 ms (for t7 ≥ 400 ms) / whichever is
                      I7 Fw/Bw = 0,6...10 In step  ± 7 % If ≤ 6 In
       D  (8)  67                                        0,1...0,8 s step =  t  = t7  higher, ± 20 ms or ± 10 % (for t7 < 400
                      = 0,1 In             ± 10 % If > 6 In              t
                                                         0,01 s                   ms)
                                                                                  The best of the two values: ± 10% or ±
                      Q27 = 0,4...2 Sn step =            t27 = 0,5...100 s
       OQ     32OF                         ± 10 %                      t  = t27   40 ms (for set time < 5 s) / ± 100 ms (for
                      0,001 Sn                           step = 0,5 s    t
                                                                                  set time ≥ 5 s)
                                                                                  The best of the two values: ± 10% or ±
                      P26 = 0,4...2 Sn step =            t26 = 0,5...100 s
       OP     32OF                         ± 10 %                      t  = t26   40 ms (for set time < 5 s) / ± 100 ms (for
                      0,001 Sn                           step = 0,5 s    t
                                                                                  set time ≥ 5 s)
                                                                                  The best of the two values: ± 10% or ±
                      P23 = 0,1...1 Sn step =            t23 = 0,5...100 s
       UP   (9)  32LF                      ± 10 %                      t  = t23   40 ms (for set time < 5 s) / ± 100 ms (for
                      0,001 Sn                           step = 0,5 s    t
                                                                                  set time ≥ 5 s)
                      Q24 = -1...-0,1 Sn step =
                      0,001 Sn; Kq = -2…2 step           t24 = 0,5...100 s        The best of the two values: ± 10% or ±
       RQ     40 / 32R                     ± 10 %                      t  = t24   40 ms (for set time < 5 s) / ± 100 ms (for
                      = 0,01; Vmin = 0,5...1,2 Un        step = 0,5 s    t        set time ≥ 5 s)
                      step = 0,01
       Cos φ  78      Cos φ = 0,5...0,95 step =
                      0,01
       (5)  calculation of t  is valid for values which have exceeded the trip threshold of the protection
                     t
       (6)  tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values
       within operating limits; the tolerance value is ± 20% if the conditions are not guaranteed
       (7)  ANSI / IEEE C37-2 codification
       (8)  the protection does not detect the fault current direction for < 5 V voltages.
       (9)  not active if the circuit-breaker is open (TRIP OFF is signaled); the protection is also active for negative active power, but is independent
       of RP protection (Protection from inverse active power)

                                                                                                Continued on the next page

       35 | © 2022 ABB |  1SDH001316R1002 - ECN000232533                                                  Protections