Page 50 - ACB-E1.2-E2.2-E4.2-E6.2
P. 50
ABB | SACE Emax 2
3 - Measurement
Presentation Two Measurement modules are available:
• Measurement enabler installed by default on Ekip Touch and enabled in the presence of the
Measuring Measurements package (enabling can be obtained both at the time the circuit-breaker
is ordered or at a later date, via Market Place)
• Measurement enabler with voltage socket is installed by default on Ekip Hi-Touch, Ekip G Touch
and Ekip G Hi-Touch; can be installed in conjunction with Ekip Touch if requested when circuit-
breaker is ordered
Both modules measure voltages, frequencies, power and energy values; in addition, the Measurement
enabler with voltage socket module allows:
• the Trip unit to be supplied directly by the voltage sockets to which it is connected
• management of the synchronism function when the Ekip Synchrocheck module is installed (see
description of module in manual 1SDH001330R1002).
Measurement performance The measurement performance provided when the Measurement modules are installed (described on
page 39), are more accurate when the Class 1 Power & Energy Metering package is present (described on
page 41.
Configurations available Both modules can be ordered with different connection configurations:
• connections to internal terminals or in an external terminal box
• connections to the upper or lower terminals of the poles on the basis of the expected power flow
• with normal or reverse pole order
For full details about ordering and the connections, consult technical catalog 1SDC200023D0906 and the
wiring diagrams 1SDM000091R0001.
Electrical characteristics The Measurement modules function correctly in the electrical conditions described on page 11.
Installations with up to 1150 VAC line-to-line voltage can be connected and configured in the presence of
connections to external sockets and an isolation transformer.
Isolation transformer The isolation transformer must conform to standard IEC 60255-27 and possess the following
characteristics:
Characteristics Description
• Accuracy class: ≤ 0,2
• Performance: ≥ 10 VA
• Overload: 20 % permanent
• Insulations: 4 kV between inputs and outputs, 4 kV between shield and
Electrical
outputs, 4 kV between shield and inputs
• Frequency: Fn +-10%
• Primary voltage: 100 to 1150 V (nominal, to be configured via menu)
• Secondary voltage: 100 to 230 V (nominal, to be configured via menu)
Parameters The specific configuration area will activate in the Settings - Modules - Ekip Measuring menu if the
Measurement module is detected correctly by the trip unit.
The following items can be configured in this menu:
• the rated voltage
• presence of the isolation transformer and the mode in which the values of the relative parameters
are selected
• the power flow
• presence of external neutral voltage (with 3P circuit-breaker)
48 | © 2022 ABB | 1SDH001316R1002 - ECN000232533 Accessories | 3 - Measurement