          6.   Press OK to return to Start window.             Press down arrow to display Ambient Light.
                                                               The ambient light warning of all inputs of
          If the system is not OK, a notification window appears   the extension. Modules (E6-S) are displayed with “1”
          displaying following:                                indicating OK and “0” indicating WARNING,

          •  System Error                                      Following are displayed:
          •  Error code.                                       •  X2: “Status message”
          •  Time and Date.                                    •  X3: “Status message”
                                                               •  Time and Date.

                                                               Following Ambient light messages are possible:

                              System Error                     •  11 11 10 11 11 (Or any Combination of 1 and 0)*
                        See TVOC-2 manual                      •  All ambient light OK
                        134 0   0   0   0   0
                       14:02  3-Feb-2009
                                        Menu                   •  All ambient light WARNING
                                                               •  Not Mounted

                                                               •  Not Available

                                                1SFC170011M0201

            Figure 48                                                                                                 05
          System Error

                                                                                   Ambient Light
          Press down arrow to display Sensor status. The status of          X2:   All ambient light OK
          all inputs of the extension modules (E6-S) are displayed          X3:   11  11  11  01  11
          with “1” indicating OK and “0” indicating FAIL,                   14:02 3-Feb-2009
                                                                           Back
          Following are displayed:
          •  X2: “Status message”

          •  X3: “Status message”                                                                    1SFC170011M0201
          •  Time and Date.                                      Figure 50
                                                                 view ambient light
          Following Status messages are possible:
          •  11 01 11 11 11 (Or any Combination of 1 and 0)*        INFORMATION
                                                                    See: “Error Log” on page 50.
          •  All sensors OK
                                                               Error Log
          •  All sensors FAIL
                                                               In the Error Log are the 6 latest system error events
          •  Not Mounted                                       stored, the oldest will be overwritten.
          •  Not Available




                             Sensor status
                        X2:   01  11  11  11  11
                        X3:   All sensors OK
                       14:02    3-Feb-2021
                      Back              Menu



                                                1SFC170011M0201
            Figure 49
          view sensor status
   36   37   38   39   40   41   42   43   44   45   46