38 ABB ARC GUARD SYSTEM™ – TVOC-2 INSTALLATION AND MAINTENANCE GUIDE
5.1 Introduction • Error LED
Error
The Human Machine Interface, HMI is used for all
communication with the user and also to confirm any
changes. If power is lost (max 48 hours) the Time and − No light in LED indicates that no error is detected in
Date will be restored. After very long power interruptions the Arc Guard System.
the Time and Date are set to a default value and needed to − Red light in LED signals that error is detected in the
be set by the user. system and the Internal Relay Fault (IRF), K1 is
de-energized.
This chapter consists of the following sections:
• Overview HMI
• Com LED
• HMI functions
Com
• HMI menus
− Yellow light indicates active communication
Prerequisites
WARNING
The reader should have knowledge and act 5.2.2 HMI Display
according to applicable safety laws and The HMI start window displays Name of Arc Guard System,
standards as well as local safety instructions.
Time and Date.
5.2 Overview HMI and HMI-COM
05
The HMI module consists of:
ABB TVOC-2
2. HMI display. 1. LED signals.
15:09
27-Feb-2009
Arc Guard System TVOC-2
TM
Menu
Com
1. LED signals. Trip
Error
Back Ok
3. Four soft keys.
1SFC170011M0201
Figure 42
HMI Display
1SFC170011M0201
The bottom of display shows the tasks assigned to the
Figure 41
Overview of the HMI four soft keys.
5.2.1 LED signals 5.2.3 Soft keys
The four LED signals are used for visual signalling and The four soft keys are used to navigate in the menu.
they are: Each key is assigned a task, displayed in the window.
• Power LED 5.3 HMI menu structure
The menu is structured in five main categories.
Each category is divided into subcategories. Some
− Green light in LED indicates that power is on. subcategories have sub-sub categories. All categories are
− No light in LED signals no power to HMI. numbered according to the structure.
• Trip LED
Trip
− Red light indicates Trip.