          5.3.1    Menu and languages                          The notification window display the following:
                                                               •  Position of activated detector.
          The Arc Monitor includes a menu shown in the display.    •  Identification of energized trip contact.
          The menu language can be chosen in the start-up
          sequence but it can also be changed during operation.  •  Time and Date of arc detection.
          Languages available in the system menu are:
                                                               To reset the Trip Signal Relays, K2 and K3 do the
                                                               following steps:
          •  English (us/uk)
                                                               1.   In the notification window press Reset.
                                                               2.   The notification window disappears and the
          5.4    HMI start menu                                     system returns to Start window.

                                                               3.   The trip is stored in the Trip Log.
          The Start menu display following main categories.
          •  Trip Log                                               INFORMATION
                                                                    If Auto reset of K2 and K3 is configured with
          •  Diagnostics
                                                                    the DIP switches, the notification window will
          •  Configuration                                          appear at a trip but there is no need to reset.
                                                                    Press Menu to return to Start window.
          •  Language

          •  Set Time and Date
                                                               Checking the trip log
          •  Factory reset
                                                               To check the Trip Log from the Start Menu do the       05
          5.4.1    Trip Log                                    following steps:
                                                               1.   Select 1. Trip Log
          When the optical detectors detect arcs, the Arc Monitor   2.   Press OK
          reacts by energizing the trip contacts according to the
          configuration of the DIP switches. The Arc Monitor is   3.   The Trip Log window displays:
          designed to save information about arc events the Trip
          Log. The Trip Log can store 7 trips in a circular buffer,   • Trip Log 1 (3), one of three in the trip log list
          where the oldest will be overwritten.                     • Position of activated detector
          This section describes how to handle the Trip Log.
                                                                    • Identification of energized trip contact

                                                                    • Time and Date of event
          Trip notification window
          When a trip occurs a notification window will be displayed
          on the display.

                                                                                  1. Trip Log 1 (3)
                                                                             Detector X1 : 10
                                                                             Breaker K4 K5
                                                                             14:02  3-Feb-2009
                             Trip has occured                              Back
                        Detector X1 : 10
                        Breaker K4 K5
                        14:02  3-feb-2009

                                        Reset                                                        1SFC170011M0201
                                                                 Figure 44
                                                               Checking the trip log

                                                1SFC170011M0201  Three detectors can be listed in the same window.
            Figure 43                                          4.   Press Back to return to Start window.
          Trip notification window
                                                               5.   Scroll down with the arrow key to see previous
                                                                    trip events.