Page 51 - Arc Guard System - TVOC-2
P. 51

ABB  ARC GUARD SYSTEM™ – TVOC-2  INSTALLATION AND MAINTENANCE GUIDE                51




         Following Status messages are possible:              The error codes are written in 6 columns. Every column
                                                              can show a number between 0 – 255.
         •  11 01 11 11 11  (Or any Combination of 1 and 0)
                      1)
         •  All sensors OK

         • All sensors FAIL

         • Not Mounted



                             Sensor status
                        X2:   01  11  11  11  11
                        X3:   All sensors OK
                       14:02    3-Feb-2021
                      Back               Menu                                                        1SFC170011M0201
                                                                Figure 60
                                                                Error codes

                                                              See: “List of error codes” on page 51.
                                                 1SFC170011M0201
          Figure 58
          view sensor status
                                                              Attending errors
         Press down arrow to display Ambient Light. The ambient
         light warning of all inputs of the extension boards   The error will exist until it is attended to and proper
         (E6-S) are displayed with “1” indicating OK and “0”   measures are taken. Then, when the Arc Monitor runs
         indicating WARNING,                                  a diagnostics the error will disappear.
                                                              To view the Error Log do the steps below:

         Following are displayed:                             1.    From the Start window, press Menu.
         • X2: “Status message”                               2.    In the Menu, select 2. Diagnostics and press OK.

         • X3: “Status message”                               3.    Select 2.3 Error Log and press OK.
         • Time and Date.                                     4.    The Error Log window displays Error code, Time,
                                                                    and Date.
                                                                                                                      07
                                                              5.    Scroll forward/backward in the Error Log.

                                                              6.    Press Back to return to window 2. Diagnostics.
                              Ambient Light                   7.    Press Back to return to Start window.
                       X2:   All ambient light OK
                       X3:   11  11  11  01  11
                       14:02 3-Feb-2009
                      Back





                                                 1SFC170011M0201
          Figure 59
          view ambient light

         Following Ambient light messages are possible:
         •  11 11 10 11 11  (Or any Combination of 1 and 0)
                      1)
         •  All ambient light OK
         •  All ambient light WARNING
         • Not Mounted

         Note:
         1)  Each number 1 or 0 indicates the position of the
            detectors actual position on the extension unit (first
            position from left on extension module X2 = X2:1)
   46   47   48   49   50   51   52   53   54   55   56