Page 847 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 847

ABB  MOTOR PROTECTION AND CONTROL                                                11/9

          —

          HF0.6, HF2.4, HF9 electronic compact starters
          Reversing starter




                                    The HF-ROL-range is used for forward and reverse running motors, as well as for switching non
                                      resistive loads. With contactor and overload relay functionalities integrated into one device, the
                                      results are faster wiring times and fewer faults. The range covers 0.6 A, 2.4 A and up to 9 A - for
                                      motors up to 3 kW – 400 V AC. The integrated electronic overload protection with tripping class 10A
                                    has a wide setting range that enables just three models to cover all requirements. The control supply
                                    voltage is 24 V DC. For the control and main connection points ABB offers screw connections.
                                    ABB also offers a HF-ROLE safety range with emergency stop function. This offers Safety Integrity
                                    Level 3, in accordance with functional safety standard IEC 61508-1 and Performance Level 'e' in
                                    accordance with ISO 13849-1 all in combination with a safety relay like ABB's Sentry SSR10. The
                                    safety range is ATEX-certified.
                        2CDC241006V0016  Rated    Rated   Rated   Setting    Full load   Type   Order code  Weight

                                                                                                           (1 pce)
                                    operational  operational  operational  range
                                                                 amps
          HF9-ROL-24VDC             current    power  current    motor use
                                    AC-53a  AC-53a  AC-51
                                    A      kW     A       A      A                                         kg
                                    Reversing starter with overload protection
                                    0.6    0.18 (400V) 0.6  0.075 … 0.6  0.6  HF0.6-ROL-24VDC  1SAT115000R1011  0.217
                                    2.4    0.75 (400V) 2.4  0.18 … 2.4   2.4  HF2.4-ROL-24VDC  1SAT125000R1011  0.219
                                    6.5    3.00 (400V) 9.0  1.5 … 9.0  6.5  HF9-ROL-24VDC  1SAT145000R1011  0.218
                                    Reversing starter with overload protection and emergency stop
                                    0.6    0.18 (400V) 0.6  0.075 … 0.6  0.6  HF0.6-ROLE-24VDC  1SAT116000R1011  0.218
                                    2.4    0.75 (400V) 2.4  0.18 … 2.4   2.4  HF2.4-ROLE-24VDC  1SAT126000R1011  0.270
                                                                 6.5
                                                          1.5 … 9.0
                                                                                      1SAT146000R1011
                                                                        HF9-ROLE-24VDC
                                    6.5
                                                                                                           0.289
                                           3.00 (400V) 9.0
                        2CDC241003V0016
          HF9-ROLE-24VDC









                                                                                                                      11











                                      Main dimensions mm, inches










                                                                                   2CDC242003F0017



                                      HF0.6, HF2.4, HF9
   842   843   844   845   846   847   848   849   850   851   852